Fire retardant cable(Fireguard)
600/1000V XLPE Insulated, PVC Sheathed, Unarmoured Power Cables to BS 7889 (Single Core)
FGD300 1RV-R (CU/XLPE/PVC 600/1000V Class 2)
BS Code: 6181X
Application:
BS 7889 CU/XLPE/PVC are mainly use in fixed installations in industrial areas, buildings and similar applications but not for burial in the ground, either directly or in ducts.
Standards:
Basic design to to BS 7889:2012
Fire Performance:
Flame Retardance (Single Vertical Wire Test) | BS EN 60332-1-2 |
---|
Voltage Rating:
600/1000V
Cable Construction:
Conductor:Annealed copper conductor, class 5 according to BS EN 60228.
Insulation:XLPE type GP8 according to BS 7655-1.3.
Inner Covering Option:The optional inner covering, where used, shall consist of an extruded layer of synthetic polymeric material. It shall surround the single core and the laid-up two, three, four or five cores, giving the assembly a practically circular shape.
Outer Sheath:PVC Type 9 according to BS 7655-4.2.
Outer Sheath Option:UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable design. LSPVC can also be provided upon request.
Colour Code:
Insulation Colour :Brown or blue
Sheath Colour:Black, other colours can be offered upon request.
Mechanical and Electrical Properties:
Maximum temperature range during operation (XLPE) | 90°C |
---|---|
Maximum short circuit temperature (5 Seconds) | 250°C |
Minimum bending radius | Circular copper conductor (OD≤25mm): 4 x Overall Diameter |
Circular copper conductor (OD>25mm): 6 x Overall Diameter |
|
Shaped copper conductor: 8 x Overall Diameter |
Construction Parameters:
Conductor | FGD300 1RV-R | ||||
---|---|---|---|---|---|
No. of Cores xCross Section | Class of Conductor | Nominal Insulation Thickness | Nominal Sheath Thickness | Nominal Overall Diameter | Approx.Weight |
No.xmm2 | mm | mm | mm | kg/km | |
1x1.5 |
2 |
0.7 |
1.4 |
6.1 |
36 |
1x2.5 |
2 |
0.7 |
1.4 |
6.8 |
52 |
1x4.0 |
2 |
0.7 |
1.4 |
7.4 |
76 |
1x6.0 |
2 |
0.7 |
1.4 |
8.2 |
100 |
1x10 |
2 |
0.7 |
1.4 |
9.2 |
160 |
1x16 |
2 |
0.7 |
1.4 |
10.7 |
230 |
1x25 |
2 |
0.9 |
1.4 |
12.5 |
340 |
1x35 |
2 |
0.9 |
1.4 |
13.5 |
440 |
1x50 |
2 |
1 |
1.4 |
13.7 |
541 |
1x70 |
2 |
1.1 |
1.4 |
15.8 |
749 |
1x95 |
2 |
1.1 |
1.5 |
17.5 |
1000 |
1x120 |
2 |
1.2 |
1.5 |
19.3 |
1241 |
1x150 |
2 |
1.4 |
1.6 |
21.5 |
1523 |
1x185 |
2 |
1.6 |
1.6 |
24.7 |
1942 |
1x240 |
2 |
1.7 |
1.7 |
27.7 |
2514 |
1x300 |
2 |
1.8 |
1.8 |
30.6 |
3125 |
1x400 |
2 |
2 |
1.9 |
34.2 |
3967 |
1x500 |
2 |
2.2 |
2 |
38 |
5063 |
1x630 |
2 |
2.4 |
2.2 |
42.9 |
6491 |
1x800 |
2 |
2.6 |
2.3 |
46 |
8075 |
1x1000 |
2 |
2.8 |
2.4 |
63 |
9860 |
ELECTRICAL PROPERTIES :
Conductor Operating Temperature :70°C
Ambient Temperature:30°C
Current-Carrying Capacities (Amp) according to BS 7671:2008 table 4E1A
Conductor cross-sectional area |
Reference Method A (enclosed in conduit in thermally insulating wall etc) | Reference Method B (enclosed in conduit on a wall or in trunking etc) | Reference Method C (clipped direct) | Reference Method F (in free air or on a perforated cable tray horizontal or vertical etc) | Reference Method G (in free air) Spaced by one cable diameter | ||||||
---|---|---|---|---|---|---|---|---|---|---|---|
2 cables, single-phase a.c. or d.c. | 3 or 4 cables, three-phase a.c. | 2 cables, single-phase a.c. or d.c | 3 or 4 cables, three-phase a.c. | 2 cables, single-phase a.c. or d.c. flat and touching | 3 or 4 cables, three-phase a.c. flat and touching or trefoil | 2 cables, single-phase a.c. or d.c. flat | 3 cables, three-phase a.c. flat | 3 cables, three-phase a.c. trefoil | 2 cables, single-phase a.c. or d.c. or 3 cables three-phase a.c. flat | ||
Horizontal | Vertical | ||||||||||
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
10 |
11 |
12 |
mm² |
A |
A |
A |
A |
A |
A |
A |
A |
A |
A |
A |
1.5 |
19 |
17 |
23 |
20 |
25 |
23 |
- |
- |
- |
- |
- |
2.5 |
26 |
23 |
31 |
28 |
34 |
31 |
- |
- |
- |
- |
- |
4 |
35 |
31 |
42 |
37 |
46 |
41 |
- |
- |
- |
- |
- |
6 |
45 |
40 |
54 |
48 |
59 |
54 |
- |
- |
- |
- |
- |
10 |
61 |
54 |
75 |
66 |
81 |
74 |
- |
- |
- |
- |
- |
16 |
81 |
73 |
100 |
88 |
109 |
99 |
- |
- |
- |
- |
- |
25 |
106 |
95 |
133 |
117 |
143 |
130 |
161 |
141 |
135 |
182 |
161 |
35 |
131 |
117 |
164 |
144 |
176 |
161 |
200 |
176 |
169 |
226 |
201 |
50 |
158 |
141 |
198 |
175 |
228 |
209 |
242 |
216 |
207 |
275 |
246 |
70 |
200 |
179 |
253 |
222 |
293 |
268 |
310 |
279 |
268 |
353 |
318 |
95 |
241 |
216 |
306 |
269 |
355 |
326 |
377 |
342 |
328 |
430 |
389 |
120 |
278 |
249 |
354 |
312 |
413 |
379 |
437 |
400 |
383 |
500 |
454 |
150 |
318 |
285 |
393 |
342 |
476 |
436 |
504 |
464 |
444 |
577 |
527 |
185 |
362 |
324 |
449 |
384 |
545 |
500 |
575 |
533 |
510 |
661 |
605 |
240 |
424 |
380 |
528 |
450 |
644 |
590 |
679 |
634 |
607 |
781 |
719 |
300 |
486 |
435 |
603 |
514 |
743 |
681 |
783 |
736 |
703 |
902 |
833 |
400 |
- |
- |
683 |
584 |
868 |
793 |
940 |
868 |
823 |
1085 |
1008 |
500 |
- |
- |
783 |
666 |
990 |
904 |
1083 |
998 |
946 |
1253 |
1169 |
630 |
- |
- |
900 |
764 |
113 |
1033 |
1254 |
1151 |
1088 |
1454 |
1362 |
800 |
- |
- |
- |
- |
1288 |
1179 |
1358 |
1275 |
1214 |
1581 |
1485 |
1000 |
- |
- |
- |
- |
1443 |
1323 |
1520 |
1436 |
1349 |
1775 |
1671 |
Voltage Drop (Per Amp Per Meter) according to BS 7671:2008 table 4E1B
Nominal Cross Section Area |
2 cables d.c. |
2 cables, single-phase a.c. | 3 or 4 cables, three-phase a.c. | |||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Ref. Methods A and B (enclosed in conduit or trunking) | Ref. Methods C, F & G(clipped direct, on trays or in free air) | Ref. Methods A & B (enclosed in conduit or trunking | Ref. Methods C, F & G (clipped direct, on trays or in free air) | |||||||||||||||
1 | 2 | 3 | Cables touching 4 | Cables spaced* 5 | 6 | 7 | ||||||||||||
mm² | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | ||||||||||||
1.5 |
31 |
|
31 |
|
|
27 |
|
|
27 |
|
|
27 |
|
|
27 |
|
||
2.5 |
19 |
|
19 |
|
|
16 |
|
|
16 |
|
|
16 |
|
|
16 |
|
||
4 |
33 |
|
12 |
|
|
10 |
|
|
10 |
|
|
10 |
|
|
10 |
|
||
6 |
7.8 |
|
7.9 |
|
|
6.8 |
|
|
6.8 |
|
|
6.8 |
|
|
6.8 |
|
||
10 |
4.7 |
|
4.7 |
|
|
4.7 |
|
|
4 |
|
|
4 |
|
|
4 |
|
||
16 |
2.9 |
|
2.9 |
|
|
2.9 |
|
|
2.5 |
|
|
2.5 |
|
|
2.5 |
|
||
|
|
r |
x |
z |
r |
x |
z |
r |
x |
z |
r |
x |
z |
r |
x |
z |
||
25 |
1.85 |
1.6 |
0.31 |
1.9 |
1.85 |
0.19 |
1.85 |
1.6 |
0.27 |
1.65 |
1.6 |
0.165 |
1.6 |
1.6 |
0.19 |
1.6 |
||
35 |
1.35 |
1.35 |
0.29 |
1.35 |
1.35 |
0.18 |
1.35 |
1.15 |
0.25 |
1.15 |
1.15 |
0.155 |
1.5 |
1.15 |
0.18 |
1.15 |
||
50 |
0.99 |
1 |
0.29 |
1.05 |
0.99 |
0.18 |
1 |
0.87 |
0.25 |
0.9 |
0.86 |
0.155 |
0.87 |
0.86 |
0.18 |
0.87 |
||
70 |
0.68 |
0.7 |
0.28 |
0.75 |
0.68 |
0.175 |
0.71 |
0.6 |
0.24 |
0.65 |
0.59 |
0.15 |
0.61 |
0.59 |
0.175 |
0.62 |
||
95 |
0.49 |
0.51 |
0.27 |
0.58 |
0.49 |
0.17 |
0.52 |
0.44 |
0.23 |
0.5 |
0.43 |
0.145 |
0.45 |
0.43 |
0.17 |
0.46 |
||
120 |
0.39 |
0.41 |
0.26 |
0.48 |
0.39 |
0.165 |
0.43 |
0.35 |
0.23 |
0.42 |
0.34 |
0.14 |
0.37 |
0.34 |
0.165 |
0.38 |
||
150 |
0.32 |
0.33 |
0.26 |
0.43 |
0.32 |
0.165 |
0.36 |
0.29 |
0.23 |
0.37 |
0.28 |
0.14 |
0.31 |
0.28 |
0.165 |
0.32 |
||
185 |
0.25 |
0.27 |
0.26 |
0.37 |
0.26 |
0.165 |
0.3 |
0.23 |
0.23 |
0.32 |
0.22 |
0.14 |
0.26 |
0.22 |
0.165 |
0.28 |
||
240 |
0.19 |
0.21 |
0.26 |
0.33 |
0.2 |
0.16 |
0.25 |
0.185 |
0.22 |
0.29 |
0.17 |
0.14 |
0.22 |
0.17 |
0.165 |
0.24 |
||
300 |
0.155 |
0.175 |
0.25 |
0.31 |
0.16 |
0.16 |
0.22 |
0.15 |
0.22 |
0.27 |
0.14 |
0.14 |
0.195 |
0.135 |
0.16 |
0.21 |
||
400 |
0.12 |
0.14 |
0.25 |
0.29 |
0.13 |
0.155 |
0.2 |
0.125 |
0.22 |
0.25 |
0.11 |
0.135 |
0.175 |
0.11 |
0.16 |
0.195 |
||
500 |
0.093 |
0.12 |
0.25 |
0.28 |
0.105 |
0.155 |
0.185 |
0.1 |
0.22 |
0.24 |
0.09 |
0.135 |
0.16 |
0.088 |
0.16 |
0.18 |
||
630 |
0.072 |
0.1 |
0.25 |
0.27 |
0.086 |
0.155 |
0.175 |
0.088 |
0.21 |
0.23 |
0.074 |
0.135 |
0.15 |
0.071 |
0.16 |
0.17 |
||
800 |
0.056 |
- |
- |
- |
0.072 |
0.15 |
0.17 |
- |
- |
- |
0.062 |
0.13 |
0.145 |
0.059 |
0.155 |
0.165 |
||
1000 |
0.045 |
- |
- |
- |
0.063 |
0.15 |
0.165 |
- |
- |
- |
0.055 |
0.13 |
0.14 |
0.05 |
0.155 |
0.165 |
Note: *Spacings larger than one cable diameter will result in a large voltage drop.
r = conductor resistance at operating temperature
x = reactance
z = impedance