Fire retardant cable(Fireguard)
600/1000V PVC Insulated, PVC Sheathed, Armoured Power Cables to BS 6346 (2-5 Cores)
FGD400 1VVMV-R (CU/PVC/PVC/SWA/PVC 600/1000V Class 2)
Application:
The cables are intended for use in fixed installations in industrial areas, buildings and similar applications.
Standards:
Basic design to BS 6346
Fire Performance:
Flame Retardance (Single Vertical Wire Test) | BS EN 50265-2-1 |
---|
Voltage Rating:
600/1000V
Cable Construction:
Conductor:Annealed copper wire, stranded according to BS 6360 class 2.
Insulation:PVC TI 1 according to BS 7655-3.1.
Bedding:Extruded PVC or taped bedding comprising two or more layers of PVC tape or other synthetic tape (for cables having a nominal conductor area of 16mm² and above).
Armouring:Galvanized steel wire
Outer Sheath:PVC TM 1 according to BS 7655-4.1.
Outer Sheath Option:UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable design. LSPVC can also be provided upon request.
Colour Code:
Insulation Colour | Two-core: Brown, blue |
---|---|
Sheath Colour | Black (other colours upon request) |
Physical AND THERMAL PROPERTIES:
Maximum temperature range during operation (PVC) | 70°C |
---|---|
Maximum short circuit temperature (5 Seconds) | 160°C |
Minimum bending radius | |
Circular copper conductors | 6 x Overall Diameter |
Shaped copper conductors | 8 x Overall Diameter |
Construction Parameters:
Conductor | FGD400 1VVMV-R | |||||||
---|---|---|---|---|---|---|---|---|
No. of Cores x Cross Section | Class of Conductor | Nominal Insulation Thickness | Nominal Bedding Thickness | Nominal Armour Wire Diameter | Nominal Sheath Thickness | Approx. Overall Diameter | Approx. Weight | |
Extruded Bedding | Taped Bedding | |||||||
No.xmm² | mm | mm | mm | mm | mm | mm | kg/km | |
2 Cores |
||||||||
2x1.5a |
2 |
0.6 |
0.8 |
0.9 |
1.4 |
12.3 |
- |
278 |
2x2.5a |
2 |
0.7 |
0.8 |
0.9 |
1.4 |
13.6 |
- |
355 |
2x4.0a |
2 |
0.8 |
0.8 |
0.9 |
1.4 |
15.1 |
- |
437 |
2x6.0a |
2 |
0.8 |
0.8 |
0.9 |
1.5 |
16.5 |
- |
524 |
2x10a |
2 |
1.0 |
0.8 |
1.25 |
1.6 |
20.1 |
- |
835 |
2x16a |
2 |
1.0 |
0.8 |
1.25 |
1.6 |
21.9 |
21.9 |
1045 |
2x25b |
2 |
1.2 |
1.0 |
1.6 |
1.7 |
23.0 |
22.6 |
1535 |
2x25a |
2 |
1.2 |
1.0 |
1.6 |
1.7 |
26.7 |
26.3 |
1608 |
2x35b |
2 |
1.2 |
1.0 |
1.6 |
1.8 |
24.8 |
24.4 |
1839 |
2x35a |
2 |
1.2 |
1.0 |
1.6 |
1.8 |
29.2 |
28.8 |
1941 |
2x50b |
2 |
1.4 |
1.0 |
1.6 |
1.9 |
27.8 |
27.4 |
1364 |
2x70b |
2 |
1.4 |
1.0 |
1.6 |
1.9 |
30.4 |
30.0 |
2328 |
2x95b |
2 |
1.6 |
1.2 |
2.0 |
2.1 |
35.5 |
34.7 |
3759 |
2x120b |
2 |
1.6 |
1.2 |
2.0 |
2.2 |
38.0 |
37.2 |
3217 |
2x150b |
2 |
1.8 |
1.2 |
2.0 |
2.3 |
41.3 |
40.5 |
3732 |
2x185b |
2 |
2.0 |
1.4 |
2.5 |
2.4 |
46.4 |
45.2 |
6669 |
2x240b |
2 |
2.2 |
1.4 |
2.5 |
2.5 |
51.2 |
50.0 |
6432 |
2x300b |
2 |
2.4 |
1.6 |
2.5 |
2.7 |
56.4 |
54.8 |
7680 |
2x400b |
2 |
2.6 |
1.6 |
2.5 |
2.9 |
61.9 |
60.3 |
12535 |
3 Cores |
||||||||
3x1.5a |
2 |
0.6 |
0.8 |
0.9 |
1.4 |
12.8 |
- |
311 |
3x2.5a |
2 |
0.7 |
0.8 |
0.9 |
1.4 |
14.1 |
- |
405 |
3x4.0a |
2 |
0.8 |
0.8 |
0.9 |
1.4 |
15.8 |
- |
510 |
3x6.0a |
2 |
0.8 |
0.8 |
1.25 |
1.5 |
18.0 |
- |
727 |
3x10a |
2 |
1.0 |
0.8 |
1.25 |
1.6 |
21.2 |
- |
998 |
3x16a |
2 |
1.0 |
0.8 |
1.25 |
1.6 |
23.1 |
23.1 |
1291 |
3x25b |
2 |
1.2 |
1.0 |
1.6 |
1.7 |
25.0 |
24.6 |
1879 |
3x25a |
2 |
1.2 |
1.0 |
1.6 |
1.7 |
28.2 |
27.8 |
1989 |
3x35b |
2 |
1.2 |
1.0 |
1.6 |
1.8 |
27.1 |
26.7 |
2286 |
3x35a |
2 |
1.2 |
1.0 |
1.6 |
1.8 |
30.8 |
30.4 |
2439 |
3x50b |
2 |
1.4 |
1.0 |
1.6 |
1.9 |
30.5 |
30.1 |
1638 |
3x70b |
2 |
1.4 |
1.2 |
2.0 |
2.0 |
35.0 |
34.2 |
3272 |
3x95b |
2 |
1.6 |
1.2 |
2.0 |
2.1 |
39.3 |
38.5 |
4789 |
3x120b |
2 |
1.6 |
1.2 |
2.0 |
2.2 |
42.2 |
41.4 |
4068 |
3x150b |
2 |
1.8 |
1.4 |
2.5 |
2.4 |
47.5 |
46.3 |
5231 |
3x185b |
2 |
2.0 |
1.4 |
2.5 |
2.5 |
51.9 |
50.7 |
8660 |
3x240b |
2 |
2.2 |
1.6 |
2.5 |
2.6 |
57.8 |
56.2 |
8395 |
3x300b |
2 |
2.4 |
1.6 |
2.5 |
2.8 |
63.2 |
61.6 |
10006 |
3x400b |
2 |
2.6 |
1.6 |
2.5 |
3.0 |
69.6 |
68.0 |
16856 |
4 Cores |
|
|||||||
4x1.5a |
2 |
0.6 |
0.8 |
0.9 |
1.4 |
13.5 |
- |
353 |
4x2.5a |
2 |
0.7 |
0.8 |
0.9 |
1.4 |
15.0 |
- |
466 |
4x4.0a |
2 |
0.8 |
0.8 |
1.25 |
1.5 |
17.8 |
- |
708 |
4x6.0a |
2 |
0.8 |
0.8 |
1.25 |
1.5 |
19.2 |
- |
850 |
4x10a |
2 |
1.0 |
0.8 |
1.25 |
1.6 |
22.8 |
- |
1186 |
4x16a |
2 |
1.0 |
1.0 |
1.6 |
1.7 |
26.3 |
25.9 |
1751 |
4x25b |
2 |
1.2 |
1.0 |
1.6 |
1.8 |
27.8 |
27.4 |
2254 |
4x25a |
2 |
1.2 |
1.0 |
1.6 |
1.8 |
30.7 |
30.3 |
2401 |
4x35b |
2 |
1.2 |
1.0 |
1.6 |
1.9 |
30.3 |
29.9 |
2769 |
4x35a |
2 |
1.2 |
1.0 |
1.6 |
1.9 |
33.7 |
33.3 |
2972 |
4x50b |
2 |
1.4 |
1.2 |
2.0 |
2.0 |
35.4 |
34.6 |
2198 |
4x70b |
2 |
1.4 |
1.2 |
2.0 |
2.1 |
39.2 |
38.4 |
3961 |
4x95b |
2 |
1.6 |
1.2 |
2.0 |
2.2 |
44.3 |
43.5 |
5891 |
4x120b |
2 |
1.6 |
1.4 |
2.5 |
2.4 |
49.3 |
48.1 |
5437 |
4x150b |
2 |
1.8 |
1.4 |
2.5 |
2.5 |
53.6 |
52.4 |
6357 |
4x185b |
2 |
2.0 |
1.6 |
2.5 |
2.6 |
59.0 |
57.4 |
10827 |
4x240b |
2 |
2.2 |
1.6 |
2.5 |
2.8 |
65.7 |
64.1 |
10363 |
4x300b |
2 |
2.4 |
1.6 |
2.5 |
3.0 |
72.0 |
70.4 |
12420 |
4x400b |
2 |
2.6 |
1.8 |
3.15 |
3.3 |
81.3 |
79.3 |
22477 |
5 Cores |
||||||||
5x1.5a |
2 |
0.6 |
0.8 |
0.9 |
1.4 |
14.3 |
- |
396 |
5x2.5a |
2 |
0.7 |
0.8 |
0.9 |
1.5 |
16.3 |
- |
538 |
5x4.0a |
2 |
0.8 |
0.8 |
1.25 |
1.5 |
19.0 |
- |
807 |
5x6.0a |
2 |
0.8 |
0.8 |
1.25 |
1.6 |
20.9 |
- |
987 |
5x10a |
2 |
1.0 |
1.0 |
1.6 |
1.7 |
25.8 |
- |
1581 |
5x16a |
2 |
1.0 |
1.0 |
1.6 |
1.7 |
28.4 |
28.0 |
2039 |
5x25a |
2 |
1.2 |
1.0 |
1.6 |
1.9 |
33.5 |
33.1 |
2840 |
5x35a |
2 |
1.2 |
1.0 |
1.6 |
1.9 |
36.6 |
36.2 |
3518 |
5x50a |
2 |
1.4 |
1.2 |
2.0 |
2.1 |
43.0 |
42.2 |
4881 |
5x70a |
2 |
1.4 |
1.2 |
2.0 |
2.2 |
48.1 |
47.3 |
6325 |
a Circular or compacted circular stranded conductor (class 2)
b Shaped stranded conductor (class 2)
ELECTRICAL PROPERTIES
Conductor Operating Temperature | 70°C |
---|---|
Ambient Temperature | 30°C |
Current-Carrying Capacities (Amp) according to BS 7671: 2008 table 4D4A
Conductor crosssectional area |
Reference Method C (clipped direct) | Reference Method E (in free air or on a perforated cable tray, horizontal or vertical) |
Reference Method D (direct in in groud or in ducting in groud. in or around buildings) |
|||
---|---|---|---|---|---|---|
1 two-core cable*, single-phase a.c. or d.c. |
1 three-or four core cable*, three-phase a.c. |
1 two-core cable*, singlephase a.c. or d.c. |
1 three-or four core cable*, three-phase a.c. |
1 two-core cable*, single-phase a.c. or d.c. |
1 three-or four core cable*, threephase a.c. |
|
1 |
2 |
3 |
4 |
5 |
6 |
7 |
mm2 |
A |
A |
A |
A |
A |
A |
1.5 |
21 |
18 |
22 |
19 |
22 |
18 |
2.5 |
28 |
25 |
31 |
26 |
29 |
24 |
4.0 |
38 |
33 |
41 |
35 |
37 |
30 |
6.0 |
49 |
42 |
53 |
45 |
46 |
38 |
10 |
67 |
58 |
72 |
62 |
60 |
50 |
16 |
89 |
77 |
97 |
83 |
78 |
64 |
25 |
118 |
102 |
128 |
110 |
99 |
82 |
35 |
145 |
125 |
157 |
135 |
119 |
98 |
50 |
175 |
151 |
190 |
163 |
140 |
116 |
70 |
222 |
192 |
241 |
207 |
173 |
143 |
95 |
269 |
231 |
291 |
251 |
204 |
169 |
120 |
310 |
267 |
336 |
290 |
231 |
192 |
150 |
356 |
306 |
386 |
332 |
261 |
217 |
185 |
405 |
348 |
439 |
378 |
292 |
243 |
240 |
476 |
409 |
516 |
445 |
336 |
280 |
300 |
547 |
469 |
592 |
510 |
379 |
316 |
400 |
621 |
540 |
683 |
590 |
- |
- |
Voltage Drop (Per Amp Per Meter) according to BS 7671: 2008 table 4D4B
Nominal Cross Section Area |
Two-core cables d.c. | Two-core cable, single-phase a.c. | Three- or four-core cable, three-phase a.c. | ||||
---|---|---|---|---|---|---|---|
1 | 2 | 3 | 4 | ||||
mm2 | mV/A/m | mV/A/m | mV/A/m | ||||
1.5 |
29 |
29 |
25 |
||||
2.5 |
18 |
18 |
15 |
||||
4.0 |
11 |
11 |
9.5 |
||||
6.0 |
7.3 |
7.3 |
6.4 |
||||
10 |
4.4 |
4.4 |
3.8 |
||||
16 |
2.8 |
2.8 |
2.4 |
||||
|
|
r |
x |
z |
r |
x |
z |
25 |
1.75 |
1.75 |
0.170 |
1.75 |
1.50 |
0.145 |
1.50 |
35 |
1.25 |
1.25 |
0.165 |
1.25 |
1.10 |
0.145 |
1.10 |
50 |
0.93 |
0.93 |
0.165 |
0.94 |
0.80 |
0.140 |
0.81 |
70 |
0.63 |
0.63 |
0.160 |
0.65 |
0.55 |
0.140 |
0.57 |
95 |
0.46 |
0.47 |
0.155 |
0.50 |
0.41 |
0.135 |
0.43 |
120 |
0.36 |
0.38 |
0.155 |
0.41 |
0.33 |
0.135 |
0.35 |
150 |
0.29 |
0.30 |
0.155 |
0.34 |
0.26 |
0.130 |
0.29 |
185 |
0.23 |
0.25 |
0.150 |
0.29 |
0.21 |
0.130 |
0.25 |
240 |
0.180 |
0.190 |
0.150 |
0.24 |
0.165 |
0.130 |
0.21 |
300 |
0.145 |
0.155 |
0.145 |
0.21 |
0.135 |
0.130 |
0.185 |
400 |
0.105 |
0.115 |
0.145 |
0.185 |
0.100 |
0.125 |
0.160 |
Note: *Spacings larger than one cable diameter will result in a large voltage drop.
r = conductor resistance at operating temperature
x = reactance
z = impedance