Firetox Flame Retardant Cables

300/500V XLPE Insulated, LSZH Sheathed Power Cables to BS 7211 (Single Core)

FTX300 05RZ1-U (CU/XLPE/LSZH 300/500V Class 1)

BS Code : 6241B

 


APPLICATION:

The cables are mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals and high-rise buildings.

STANDARDS:

Basic design to BS 7211:2012

FTX300 05RZ1-U (CU/XLPE/LSZH 300/500V Class 1)

FIRE PERFORMANCE:

Flame Retardance (Single vertical wire or cable test)

IEC 60332-1-2; EN 60332-1-2

Reduced Fire Propagation (Vertically-mounted bundled wires & cables test)

IEC 60332-3-24; EN 60332-3-24

Halogen Free

IEC 60754-1; EN 50267-2-1

No Corrosive Gas Emission

IEC 60754-2; EN 50267-2-2

Minimum Smoke Emission

IEC 61034-2; EN 61034-2

VOLTAGE RATING:

300/500V

CABLE CONSTRUCTION:

Conductor : Annealed copper conductor, solid according to BS EN 60228 class 1.

Insulation : XLPE type GP8 according to BS 7655-1.3. Crosslinked polyolefin material type EI 5 according to EN 50363-5 can be offered as option.

CPC (Circuit Protective Conductor) : Uninsulated copper conductor.

Outer Sheath : Extruded LSZH type LTS 2 according to BS 7655-6.1.

Outer Sheath Option : UV resistance, hydrocarbon resistance, oil resistance, anti-rodent and anti-termite properties can be offered as option.

COLOUR CODE:

Insulation Colour : Brown or blue.

Sheath Colour : White; other colours can be offered upon request.

PHYSICAL AND THERMAL PROPERTIES:

Maximum temperature range during operation : 90°C

Maximum short circuit temperature (5 Seconds) : 250°C

Minimum bending radius : 4 x Overall Diameter

CONSTRUCTION PARAMETERS:

Conductor FTX300 05RZ1-U
No. of Cores × Cross-sectional Area Conductor Class Nominal Insulation Thickness Cross- sectional Area of CPC Class of CPC Nominal Insulation Thickness Min. overall Dimensions Max. overall Dimensions Approx. Weight
No.×mm²   mm mm²   mm mm mm kg/km

1×1.0

1

0.70

1.0

1

0.9

4.1x5.2

5.0x6.3

45

1×1.5

1

0.70

1.0

1

0.9

4.4x5.4

5.3x6.6

55

ELECTRICAL PROPERTIES:

Conductor operating temperature : 90°C

Ambient temperature : 30°C

Current-Carrying Capacities (Amp) according to BS 7671:2008 table 4E1A

Conductor cross- ectional area Ref. Method A (enclosed in conduit in thermally insulating wall etc.) Ref. Method B (enclosed in conduit on a wall or in trunking etc.) Ref. Method C (clipped direct)
2 cables, single-phase a.c. or d.c. 3 or 4 cables, three-phase a.c. 2 cables, single-phase a.c. or d.c 3 or 4 cables, three-phase a.c. 2 cables, single- phase a.c. or d.c. flat and touching 3 or 4 cables, three-phase a.c. flat and touching or trefoil

1

2

3

4

5

6

7

mm²

A

A

A

A

A

A

1.0

14

13

17

15

19

17.5

1.5

19

17

23

20

25

23

Voltage Drop (Per Amp Per Meter) according to BS 7671:2008 table 4E1B

             
Conductor cross- sectional area 2 cables d.c. 2 cables, single-phase a.c. 3 or 4 cables, three-phase a.c.
Ref. Methods A&B (enclosed in conduit or trunking) Ref. Methods C, F&G (clipped direct, on trays or in free air) Ref. Methods A&B (enclosed in conduit or trunking) Ref. Methods C, F&G (clipped direct, on trays or in free air)
Cables touching, Trefoil Cables touching, flat Cables spaced*, flat
Cables touching Cables spaced*
1 2 3 4 5 6 7 8 9
mm² mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m

1.0

46

46

46

46

40

40

40

40

1.5

31

31

31

31

27

27

27

27

Note: *Spacings larger than one cable diameter will result in a large voltage drop.