Firetox Flame Retardant Cables
300/500V XLPE Insulated, LSZH Sheathed Power Cables to BS 7211 (Single Core)
FTX300 05RZ1-U (CU/XLPE/LSZH 300/500V Class 1)
BS Code : 6241B
APPLICATION:
The cables are mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals and high-rise buildings.
STANDARDS:
Basic design to BS 7211:2012
FIRE PERFORMANCE:
Flame Retardance (Single vertical wire or cable test) | IEC 60332-1-2; EN 60332-1-2 |
---|---|
Reduced Fire Propagation (Vertically-mounted bundled wires & cables test) | IEC 60332-3-24; EN 60332-3-24 |
Halogen Free | IEC 60754-1; EN 50267-2-1 |
No Corrosive Gas Emission | IEC 60754-2; EN 50267-2-2 |
Minimum Smoke Emission | IEC 61034-2; EN 61034-2 |
VOLTAGE RATING:
300/500V
CABLE CONSTRUCTION:
Conductor : Annealed copper conductor, solid according to BS EN 60228 class 1.
Insulation : XLPE type GP8 according to BS 7655-1.3. Crosslinked polyolefin material type EI 5 according to EN 50363-5 can be offered as option.
CPC (Circuit Protective Conductor) : Uninsulated copper conductor.
Outer Sheath : Extruded LSZH type LTS 2 according to BS 7655-6.1.
Outer Sheath Option : UV resistance, hydrocarbon resistance, oil resistance, anti-rodent and anti-termite properties can be offered as option.
COLOUR CODE:
Insulation Colour : Brown or blue.
Sheath Colour : White; other colours can be offered upon request.
PHYSICAL AND THERMAL PROPERTIES:
Maximum temperature range during operation : 90°C
Maximum short circuit temperature (5 Seconds) : 250°C
Minimum bending radius : 4 x Overall Diameter
CONSTRUCTION PARAMETERS:
Conductor | FTX300 05RZ1-U | |||||||
---|---|---|---|---|---|---|---|---|
No. of Cores × Cross-sectional Area | Conductor Class | Nominal Insulation Thickness | Cross- sectional Area of CPC | Class of CPC | Nominal Insulation Thickness | Min. overall Dimensions | Max. overall Dimensions | Approx. Weight |
No.×mm² | mm | mm² | mm | mm | mm | kg/km | ||
1×1.0 |
1 |
0.70 |
1.0 |
1 |
0.9 |
4.1x5.2 |
5.0x6.3 |
45 |
1×1.5 |
1 |
0.70 |
1.0 |
1 |
0.9 |
4.4x5.4 |
5.3x6.6 |
55 |
ELECTRICAL PROPERTIES:
Conductor operating temperature : 90°C
Ambient temperature : 30°C
Current-Carrying Capacities (Amp) according to BS 7671:2008 table 4E1A
Conductor cross- ectional area | Ref. Method A (enclosed in conduit in thermally insulating wall etc.) | Ref. Method B (enclosed in conduit on a wall or in trunking etc.) | Ref. Method C (clipped direct) | |||
---|---|---|---|---|---|---|
2 cables, single-phase a.c. or d.c. | 3 or 4 cables, three-phase a.c. | 2 cables, single-phase a.c. or d.c | 3 or 4 cables, three-phase a.c. | 2 cables, single- phase a.c. or d.c. flat and touching | 3 or 4 cables, three-phase a.c. flat and touching or trefoil | |
1 |
2 |
3 |
4 |
5 |
6 |
7 |
mm² |
A |
A |
A |
A |
A |
A |
1.0 |
14 |
13 |
17 |
15 |
19 |
17.5 |
1.5 |
19 |
17 |
23 |
20 |
25 |
23 |
Voltage Drop (Per Amp Per Meter) according to BS 7671:2008 table 4E1B
Conductor cross- sectional area | 2 cables d.c. | 2 cables, single-phase a.c. | 3 or 4 cables, three-phase a.c. | |||||
---|---|---|---|---|---|---|---|---|
Ref. Methods A&B (enclosed in conduit or trunking) | Ref. Methods C, F&G (clipped direct, on trays or in free air) | Ref. Methods A&B (enclosed in conduit or trunking) | Ref. Methods C, F&G (clipped direct, on trays or in free air) | |||||
Cables touching, Trefoil | Cables touching, flat | Cables spaced*, flat | ||||||
Cables touching | Cables spaced* | |||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 |
mm² | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m |
1.0 |
46 |
46 |
46 |
46 |
40 |
40 |
40 |
40 |
1.5 |
31 |
31 |
31 |
31 |
27 |
27 |
27 |
27 |
Note: *Spacings larger than one cable diameter will result in a large voltage drop.