Firetox Flame Retardant Cables
300/500V LSZH Insulated, Non-sheathed Power Cables to BS EN 50525-3-41 (Single Core)
FTX100 05Z-U/K (CU/LSZH 300/500V Class 1/5)
BS Code: 2491B
HAR Code: H05Z-U/K
APPLICATION:
The cables are mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals and high-rise buildings.
STANDARDS:
Basic design to BS EN 50525-3-41(formerly BS 7211)
FIRE PERFORMANCE:
Flame Retardance (Single vertical wire or cable test) | IEC 60332-1-2; EN 60332-1-2 |
---|---|
Halogen Free | IEC 60754-1; EN 50267-2-1 |
No Corrosive Gas Emission | IEC 60754-2; EN 50267-2-2 |
Minimum Smoke Emission | IEC 61034-2; EN 61034-2 |
VOLTAGE RATING:
300/500V
CABLE CONSTRUCTION:
Conductor : Copper conductor according to BS EN 60228 class 1/2/5.
Insulation : Crosslinked polyolefin material type EI 5 according to EN 50363-5.
Insulation Option : UV resistance, hydrocarbon resistance, oil resistance, anti-rodent and anti-termite properties can be offered as option.
COLOUR CODE:
Black, Blue, Brown, Grey, Orange, Pink, Red, Turquoise, Violet, White, Green and Yellow. Bi-colours of any
combination of the above mono-colours are permitted.
PHYSICAL AND THERMAL PROPERTIES:
Maximum temperature range during operation : 90°C
Maximum short circuit temperature (5 Seconds) : 250°C
Minimum bending radius : 4 x Overall Diameter
CONSTRUCTION PARAMETERS:
Conductor | FTX100 05Z-U/K | ||||
---|---|---|---|---|---|
No. of Cores × Cross-sectional Area | Conductor Class | Nominal Insulation Thickness | Min. Overall Diameter | Max. Overall Diameter | Approx. Weight |
No.×mm² | mm | mm | mm | kg/km | |
1×0.50 |
1 |
0.6 |
1.9 |
2.4 |
9.4 |
1×0.75 |
1 |
0.6 |
2.1 |
2.6 |
12.2 |
1×1.0 |
1 |
0.6 |
2.2 |
2.8 |
15.4 |
1×0.50 |
5 |
0.6 |
2.1 |
2.6 |
9.9 |
1×0.75 |
5 |
0.6 |
2.2 |
2.8 |
13.3 |
1×1.0 |
5 |
0.6 |
2.4 |
2.9 |
16.2 |
ELECTRICAL PROPERTIES:
Conductor operating temperature : 90°C
Ambient temperature : 30°C
Current-Carrying Capacities (Amp)
Conductor cross-sectional area | Single-phase a.c. | Three-phase a.c. |
---|---|---|
mm² |
A |
A |
0.5 |
3 |
3 |
0.75 |
6 |
6 |
1.0 |
10 |
10 |
Note: These values apply to the majority of cases. Further information should be sought in unusual cases eg.: |
Voltage Drop (Per Amp Per Meter)
Conductor cross-sectional area | 2 cables d.c. | 2 cables, single-phase a.c. | 3 or 4 cables, three-phase a.c. | |||||
---|---|---|---|---|---|---|---|---|
Ref. Methods A&B (enclosed in conduit or trunking) | Ref. Methods C, F&G (clipped direct, on trays or in free air) | Ref. Methods A&B (enclosed in conduit or trunking) | Ref. Methods C, F&G (clipped direct, on trays or in free air) | |||||
Cables touching | Cables spaced* | Cables touching, Trefoil | Cables touching, flat | Cables spaced*, flat | ||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 |
mm² | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m |
0.5 |
101 |
101 |
101 |
101 |
87 |
87 |
87 |
87 |
0.75 |
68 |
68 |
68 |
68 |
59 |
59 |
59 |
59 |
1.0 |
50 |
50 |
50 |
50 |
44 |
44 |
44 |
44 |
Note: *Spacings larger than one cable diameter will result in a large voltage drop.