Flame Retardant Fiber Optic Cables
Flame Retardant Tight Buffered Distribution Fiber Optic cables
MTA-B-C-D-H
Application :
This cables are used for interconnection of distribution boxes and end devices, where continued functionality is required during a fire situation. The cables are very suitable for various indoor and outdoor applications, including routing between buildings within ducts and inside building up to riser shafts.
Standards:
Basic design to Telcordia GR409-CORE / TIA/EIA 568B.3 / ICEA-S-83-596
Fire Performance:
Flame Retardance (Single Vertical Wire Test) | EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2- 1*; DIN VDE 0482-265-2-1* |
---|---|
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test) | EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30- 004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2- 4 |
Halogen Free | IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1* |
No Corrosive Gas Emission | IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2* |
minimum Smoke Emission | IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268- 1&2*; BS 7622-1&2* |
No Toxic gases | NES 02-713; NF C 20-454 |
Note: Asterisk * denotes superseded standard.
Cable Construction :
Optical fibers: Singlemode and multimode tight fibers, with tight buffer coating.
Reinforcement: Either aramid yarn or fiber glass is wound around the tube to provide physical protection and tensile strength, with added fire protection.
Inner Sheath(optional): Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1
Ripcord(optional): An optional ripcord can be located under the outer sheath to facilitate jacket removal.
Armouring(optional):
STA: Corrugated steel tape armour
SWB: Steel wire braid
Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.)
Physical And Thermal Properties:
Temperature range during operation (fixed state): -20°C - +60°C
Temperature range during installation (mobile state): 0°C - +50°C
Minimum bending radius: 10 times the outer diameter for unarmoured cables 20 times the outer diameter for
armoured cables
Electrical Properties:
AWG | 14 | |
---|---|---|
Nominal Conductor Diameter | mm | 1.6 |
Impedance | Ω | 75+/-5 |
Nominal Attenuation@100mHz | dB/100m | 4.5 |
Nominal Attenuation@270mHz | dB/100m | 7.6 |
Nominal Attenuation@540mHz | dB/100m | 10.8 |
Nominal Attenuation@750mHz | dB/100m | 12.8 |
Nominal Attenuation@1000mHz | dB/100m | 14.8 |
Capacitance | pF/m | 53.5 |
Velocity of Propagation | % | 83 |
Conductor DCR | Ω/km | 8.5 |
Shield DCR | Ω/km | 12.1 |
Inductance | μH/m | 0.32 |
Time Delay | ns/m | 4 |
Construction Parameters:
Cable Code | N° of Fibers |
Nominal Overall Diameter |
max. Tensile Strength |
minimum Bending Radius |
Approx. Weight |
---|---|---|---|---|---|
mm | N | mm | kg/km | ||
mTA-B-2-0-H | 2 | 7,6 | 250 | 76 | 55 |
mTA-B-4-0-H | 4 | 7,8 | 250 | 78 | 67 |
mTA-B-6-0-H | 6 | 8,6 | 400 | 86 | 77 |
mTA-B-8-0-H | 8 | 8,8 | 400 | 88 | 81 |
mTA-B-12-0-H | 12 | 9,3 | 400 | 93 | 90 |