Marine Cable

P15 UX 0.6/1kV


Applications :

Marine cables are flame retardant, low smoke and halogen free, used for earthing and bonding services.

Standards :

IEC 60092-353

IEC 60092-360

IEC 60332-1

IEC 60332-3-22

IEC 60754-1,2

IEC 61034-1,2

NEK 606

IEC60092 Offshore & Marine CablesIEC60092 Offshore & Marine Cables

Construction :

Conductors : Tinned annealed stranded copper to IEC 60228 class 2 or class 5.

Insulation : Halogen free thermosetting compound, SHF2. When used as protective earth (PE) wire, the cables

coloured yellow/green. When used as single wire, the cables coloured off-white, black, red or blue.

Electrical Characteristics :

    Nominal Cross Section Area mm² 10 16 25 35 50 70
    Nominal Conductor Diameter mm 4 5.1 6.5 7.4 8.7 10.3
    Maximum DC Resistant@20℃ Ω/km 1.84 1.16 0.734 0.529 0.391 0.27
    Continuous Current Rating@45℃1 Core A 72 96 127 157 196 242
    Short Circuit Current 1s A 1430 2290 3580 5010 7150 10020
    Operating Voltage KV 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1

 

    Nominal Cross Section Area mm² 95 120 150 185 240 300
    Nominal Conductor Diameter mm 12.2 13.8 15.1 17.0 19.6 21.9
    Maximum DC Resistant@20℃ Ω/km 0.195 0.154 0.126 0.1 0.0762 0.0607
    Continuous Current Rating@45℃1 Core A 293 339 389 444 522 601
    Short Circuit Current 1s A 13590 17170 21460 26470 34340 42930
    Operating Voltage KV 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1

Mechanical and Thermal Properties :

Bending Radius : 8×OD (during installation); 6×OD (fixed installed).

Temperature Range : -20℃ ~ +90℃.

Dimensions and Weight :

Construction No. of cores×Cross section
(mm²)
Nominal Insulation Thickness
mm
Nominal Overall Diameter
mm
Nominal Weight kg/km
1×10 1.0 6.6 125
1×16 1.0 7.7 185
1×25 1.2 9.5 290
1×35 1.2 10.4 380
1×50 1.4 12.1 510
1×70 1.4 13.6 700
1×95 1.6 15.5 950
1×120 1.6 17.5 1205
1×150 1.8 19.4 1470
1×185 2.0 21.7 1875
1×240 2.2 24.7 2420
1×300 2.4 27.2 3060