Applications:

Marine cables are partially water blocked, flame retardant, low smoke, halogen free and mud resistant, used for fixed installation for medium voltage power.

Standards:

IEC 60092-353

IEC 60092-360

IEC 60332-1

IEC 60332-3-22

IEC 60754-1,2

IEC 61034-1,2

NEK 606

VG 95218 part 29 

Water Blocked P2 or P2/P9 RFOU/TFOU 3.6/6KV

Construction :

Conductors: Circular tinned annealed stranded copper to IEC 60228 class 2.

Conductor Screen: Semi conducting material.

Insulation: Halogen-free EPR. XLPE can be offered as an option (for TFOU cable).

Insulation Screen: Semi conducting material and tinned copper wire braid.

Filler: Water blocking fillers, if required.

Bedding: Halogen free compound, PETP wrapping tape will be applied over the bedding, if required.

Armour: Tinned copper wire braid, PETP wrapping tape will be applied over the braiding, if required.

Water Blocking Elements: Water blocking tape and strings for providing longitudinal water tightness.

Inner Sheath: Halogen free thermosetting compound, SHF2 (for TYPE P2), or halogen free mud resistant thermosetting compound, SHF MUD (for TYPE P2/P9), coloured red.

Outer Sheath: Polyurethane for providing transversal water tightness, PE is optional,but can not meet low smoke standard.

Electrical Characteristics :

    Nominal Cross Section Area mm² 16 25 35 50 70 95 120
    Nominal Conductor Diameter mm 5.1 6.5 7.4 8.7 10.3 12.2 13.8
    Maximum DC Resistant@20℃ Ω/km 1.16 0.734 0.529 0.391 0.27 0.195 0.154
    Continuous Current Rating@45℃1 Core A 96 127 157 196 242 293 339
    Continuous Current Rating@45℃3 Core A 67 89 110 137 169 205 237
    Short Circuit Current 1s A 2290 3580 5010 7150 10020 13590 17170
    Operating Voltage KV 3.6/6 3.6/6 3.6/6 3.6/6 3.6/6 3.6/6 3.6/6

    Nominal Cross Section Area mm² 150 185 240 300 400 500 630
    Nominal Conductor Diameter mm 15.1 17.0 19.6 21.9 24.6 27.6 32.5
    Maximum DC Resistant@20℃ Ω/km 0.126 0.1 0.0762 0.0607 0.0475 0.0369 0.0286
    Continuous Current Rating@45℃1 Core A 389 444 522 601 690 780 890
    Continuous Current Rating@45℃3 Core A 272 311 365 421 483 546 623
    Short Circuit Current 1s A 21460 26470 34340 42930 57230 71540 90140
    Operating Voltage KV 3.6/6 3.6/6 3.6/6 3.6/6 3.6/6 3.6/6 3.6/6

Ambient Temperature Correction Factors :

    Ambient Temperature Correction Factors 35 40 45 50 55 60 65 70 75 80
    Rating Factor 1.1 1.05 1.0 0.94 0.88 0.82 0.74 0.67 0.58 0.47

Mechanical and Thermal Properties :

Bending Radius :15×OD (during installation); 9×OD (fixed installed).

Temperature Range : -20℃ ~ +90℃

Dimensions and Weight :

Construction No. of cores×Cross section mm² Nominal Insulation Thickness mm Nominal BeddingThickness mm NominalInner Sheath Thickness mm NominalOuter Sheath Thickness mm
Nominal Overall Diametermm Nominal Weight kg/km
1×16 2.5 1.4 1.1 1 24.8±2 819
1×25 2.5 1.5 1.1 1.2 26.4±2 1071
1×35 2.5 1.5 1.2 1.2 27.5±2 1213
1×50 2.5 1.6 1.2 1.2 28.7±2 1386
1×70 2.5 1.6 1.3 1.2 30.6±2 1675
1×95 2.5 1.7 1.3 1.4 32.8±2 2000
1×120 2.5 1.8 1.4 1.4 34.6±2 2347
1×150 2.5 1.8 1.4 1.4 36.3±2 2678
1×185 2.5 1.9 1.5 1.4 38.0±2 3166
1×240 2.6 2 1.5 1.6 42.0±2 3911
1×300 2.8 2.1 1.6 1.6 45.5±2 4856
1×400 3 2.2 1.7 1.6 49.8±2 5691
1×500 3.2 2.4 1.8 1.6 54.0±2 6941
1×630 3.2 2.5 1.9 1.6 58.3±2 8579
3×16 2.5 2.2 1.6 1 46.9±2 3077
3×25 2.5 2.3 1.7 1.2 47.8±2 3560
3×35 2.5 2.4 1.8 1.2 50.0±2 4011
3×50 2.5 2.5 1.9 1.2 53.3±2 4720
3×70 2.5 2.7 2 1.2 57.2±2 5864
3×95 2.5 2.8 2.1 1.4 61.7±2 7103
3×120 2.5 3 2.2 1.4 66.3±2 8573
3×150 2.5 3.1 2.3 1.4 70.2±2 9970
3×185 2.5 3.3 2.4 1.4 78.6±2 11193
3×240 2.6 3.5 2.5 1.6 85.5±2 12243
3×300 2.8 3.8 2.7 1.6 92.5±2 13587