HOMEPRODUCTS MARINE CABLES

 

Water Blocked

P30 RFOU-HCF / TFOU-HCF 6/10(12) kV

 

Applications :

Marine cables are partially water blocked, fire resistant, flame retardant, low smoke and halogen free, used for emergency control, power and lighting systems that need to be operational during a 1100˚C hydrocarbon fire.

Standards:

IEC 60092-354

IEC 60092-360

IEC 60332-1

IEC 60331-21

IEC 60332-3-22

IEC 60754-1,2

IEC 61034-1,2

NEK 606

VG 95218 part 29 

Construction :

IEC60092 Offshore & Marine Cables

Conductors: Circular tinned annealed stranded copper to IEC 60228 class 2.

Conductor Screen: Semi conducting material.

Insulation: Halogen-free EPR. XLPE can be offered as an option.

Insulation Screen: Semi conducting material and tinned copper wire braid.

Filler: Water blocking fillers, if required.

Bedding: Halogen free compound, PETP wrapping tape will be applied over the bedding, if required.

Armour: Tinned copper wire braid, PETP wrapping tape will be applied over the braiding, if required.

Water Blocking Elements: Water blocking tape and strings for providing longitudinal water tightness.

Inner Sheath: Halogen free thermosetting compound, SHF2, coloured red.

HC-fire protection: Extruded thermoplastic fire protection compound.

Taping: Lapped glass fibre tape.

Outer Sheath 1: Flame retardant halogen-free thermoplastic compound, SHF1, coloured red.

Outer Sheath 2: Polyurethane for providing transversal water tightness, PE is optional,but can not meet low smoke standard.

Optional

P31 RFOU-HCF / TFOU-HCF 8.7/15kV

P32 RFOU-HCF / TFOU-HCF 12/20(24) kV

P33 RFOU-HCF / TFOU-HCF 18/30(36) kV

Electrical Characteristics :

    Nominal Cross Section Area mm² 70 95 120 150 185 240 300
    Nominal Conductor Diameter mm 10.3 12.2 13.8 15.1 17.0 19.6 21.9
    Maximum DC Resistant@20℃ Ω/km 0.27 0.195 0.154 0.126 0.1 0.0762 0.0607
    Continuous Current Rating@45℃1 Core A 242 293 339 389 444 522 601
    Continuous Current Rating@45℃3 Core A 169 205 237 272 311 365 421
    Short Circuit Current 1s A 10020 13590 17170 21460 26470 34340 42930
    Operating Voltage KV 6/10 6/10 6/10 6/10 6/10 6/10 6/10

Ambient Temperature Correction Factors :

    Ambient Temperature Correction Factors 35 40 45 50 55 60 65 70 75 80
    Rating Factor 1.1 1.05 1.0 0.94 0.88 0.82 0.74 0.67 0.58 0.47

Mechanical and Thermal Properties:

Bending Radius : 25×OD (during installation); 12×OD (fixed installed).

Temperature Range : -20℃ ~ +90℃.

Dimensions and Weight :

Construction No. of cores×Cross section (mm²)
Nominal Insulation Thickness
mm
Nominal Diameter Over Bedding
mm
Nominal Diameter Over Inner Sheath mm Nominal Overall Diameter
mm
Nominal Weight
kg/km
1×70 3.4 23.5 30 64.4±2 5481
1×95 3.4 25.5 32 67.3±2 6195
1×120 3.4 27.5 34 69.3±2 6657
1×150 3.4 28.5 35 70.3±2 7004
1×185 3.4 30.5 36.5 71.8±2 7686
1×240 3.4 33 39 75.2±2 8663
1×300 3.4 35 41.5 77.7±2 9744
3×50 3.4 47 55 91.4±2 11519
3×95 3.4 54 62.5 99.8±2 14942
3×150 3.4 60 70.5 108.8±2 18270