HOMEPRODUCTS MARINE CABLES

 

Water Blocked P4 or P4/P11 RFOU/TFOU 8.7/15KV

 

Applications

    Marine cables are partially water blocked, flame retardant, low smoke, halogen free and mud resistant, used for fixed installation for medium voltage power.

Standards

IEC 60092-353

IEC 60092-360

IEC 60332-1

IEC 60332-3-22

IEC 60754-1,2

IEC 61034-1,2

NEK 606

VG 95218 part 29

Water Blocked P4 or P4/P11 RFOU/TFOU 8.7/15KV

Construction

Conductors: Circular tinned annealed stranded copper to IEC 60228 class 2.

Conductor Screen: Semi conducting material.

Insulation: Halogen-free EPR. XLPE can be offered as an option (for TFOU cable).

Insulation Screen: Semi conducting material and tinned copper wire braid.

Filler: Water blocking fillers, if required.

Bedding: Halogen free compound, PETP wrapping tape will be applied over the bedding, if required.

Armour: Tinned copper wire braid, PETP wrapping tape will be applied over the braiding, if required.

Water Blocking Elements: Water blocking tape and strings for providing longitudinal water tightness.

Inner Sheath: Halogen free thermosetting compound, SHF2 (for TYPE P4), or halogen free mud resistant thermosetting compound, SHF MUD (for TYPE P4/P11), coloured red.

Outer Sheath: Polyurethane for providing transversal water tightness, PE is optional,but can not meet low smoke standard.

Electrical Characteristics

    Nominal Cross Section Area mm² 25 35 50 70 95 120
    Nominal Conductor Diameter mm 6.5 7.4 8.7 10.3 12.2 13.8
    Maximum DC Resistant@20℃ Ω/km 0.734 0.529 0.391 0.27 0.195 0.154
    Continuous Current Rating@45℃1 Core A 127 157 196 242 293 339
    Continuous Current Rating@45℃3 Core A 89 110 137 169 205 237
    Short Circuit Current 1s A 3580 5010 7150 10020 13590 17170
    Operating Voltage KV 8.7/15 8.7/15 8.7/15 8.7/15 8.7/15 8.7/15

 

    Nominal Cross Section Area mm² 150 185 240 300 400 500 630
    Nominal Conductor Diameter mm 15.1 17.0 19.6 21.9 24.5 27.5 32.3
    Maximum DC Resistant@20℃ Ω/km 0.126 0.1 0.0762 0.0607 0.0475 0.0369 0.0286
    Continuous Current Rating@45℃1 Core A 389 444 522 601 690 780 890
    Continuous Current Rating@45℃3 Core A 272 311 365 421 483 546 623
    Short Circuit Current 1s A 21460 26470 34340 42930 57230 71540 90140
    Operating Voltage KV 8.7/15 8.7/15 8.7/15 8.7/15 8.7/15 8.7/15 8.7/15

Ambient Temperature Correction Factors

    Ambient Temperature Correction Factors 35 40 45 50 55 60 65 70 75 80
    Rating Factor 1.1 1.05 1.0 0.94 0.88 0.82 0.74 0.67 0.58 0.47

Mechanical and Thermal Properties

Bending Radius :15×OD (during installation); 9×OD (fixed installed).

Temperature Range : -20℃ ~ +90℃.

Dimensions and Weight

Construction No. of cores×Cross section (mm²) Nominal Insulation Thickness mm Nominal Bedding Thickness mm Nominal Inner Sheath Thickness mm Nominal Outer Sheath Thickness mm Nominal Overall Diameter mm Nominal Weight kg/km
1×150 4.5 2 1.5 1.4 40.9±2 3087
1×185 4.5 2 1.5 1.4 43.4±2 3722
1×240 4.5 2.1 1.6 1.6 46.6±2 4431
1×300 4.5 2.2 1.7 1.6 49.5±2 5324
1×400 4.5 2.4 1.8 1.6 53.4±2 6048
1×500 4.5 2.5 1.8 1.6 56.8±2 7224
1×630 4.5 2.6 1.9 1.6 61.1±2 8883
3×25 4.5 2.6 1.9 1.2 57.7±2 4961
3×35 4.5 2.7 2 1.2 59.9±2 5476
3×50 4.5 2.8 2 1.2 63.0±2 6258
3×70 4.5 2.9 2.1 1.2 66.8±2 7387
3×95 4.5 3.1 2.2 1.4 71.5±2 8789
3×120 4.5 3.2 2.3 1.4 75.5±2 10232
3×150 4.5 3.4 2.4 1.4 79.6±2 11697
3×185 4.5 3.6 2.6 1.4 87.0±2 14165
3×240 4.5 3.8 2.7 1.6 93.8±2 16653
3×300 4.5 4 2.9 1.6 99.8±2 19236