HOMEPRODUCTS MARINE CABLES

 

Water Blocked P7 or P7/P14 BFOU 6/10kV

 

Applications :

Marine cables are partially water blocked, fire resistant, flame retardant, low smoke, halogen free and mud resistant, used for fixed installation for medium voltage power.

Standards :

IEC 60092-354

IEC 60092-360

IEC 60332-1

IEC 60331-21

IEC 60332-3-22

IEC 60754-1,2

IEC 61034-1,2

NEK 606

VG 95218 part 29 

Water Blocked P7r P7/P14 BFOU 6/10kV

Construction:

Conductors: Circular tinned annealed stranded copper to IEC 60228 class 2.

Conductor Screen: Semi conducting material.

Insulation: Mica tape + Halogen free EPR.

Insulation Screen: Semi conducting material and tinned copper wire braid.

Filler: Water blocking fillers, if required.

Bedding: Halogen free compound, PETP wrapping tape will be applied over the bedding, if required.

Armour: Tinned copper wire braid, PETP wrapping tape will be applied over the braiding, if required.

Water Blocking Elements: Water blocking tape and strings for providing longitudinal water tightness.

Inner Sheath: Halogen free thermosetting compound, SHF2 (for TYPE P7), or halogen free mud resistant thermosetting compound, SHF MUD (for TYPE P7/P14), coloured red.

Outer Sheath: Polyurethane for providing transversal water tightness, PE is optional,but can not meet low smoke standard.

Electrical Characteristics :

    Nominal Cross Section Area mm² 25 35 50 70 95 120 150
    Nominal Conductor Diameter mm 6.5 7.4 8.7 10.3 12.2 13.8 15.1
    Maximum DC Resistant@20℃ Ω/km 0.734 0.529 0.391 0.27 0.195 0.154 0.126
    Continuous Current Rating@45℃1 Core A 127 157 196 242 293 339 389
    Continuous Current Rating@45℃3 Core A 89 110 137 169 205 237 272
    Short Circuit Current 1s A 3580 5010 7150 10020 13590 17170 21460
    Operating Voltage KV 6/10 6/10 6/10 6/10 6/10 6/10 6/10

 

    Nominal Cross Section Area mm² 185 240 300 400 500 630
    Nominal Conductor Diameter mm 17.0 19.6 21.9 24.5 27.5 32.3
    Maximum DC Resistant@20℃ Ω/km 0.1 0.0762 0.0607 0.0475 0.0369 0.0286
    Continuous Current Rating@45℃1 Core A 444 522 601 690 780 890
    Continuous Current Rating@45℃3 Core A 311 365 421 483 546 623
    Short Circuit Current 1s A 26470 34340 42930 57230 71540 90140
    Operating Voltage KV 6/10 6/10 6/10 8.7/15 8.7/15 8.7/15

Ambient Temperature Correction Factors:

Ambient Temperature Correction Factors 35 40 45 50 55 60 65 70 75 80
Rating Factor 1.1 1.05 1.0 0.94 0.88 0.82 0.74 0.67 0.58 0.47

Mechanical and Thermal Properties:

Bending Radius :15×OD (during installation); 9×OD (fixed installed).

Temperature Range : -20℃ ~ +90℃.

Dimensions and Weight :

Construction No. of cores×Cross section mm² Nominal Insulation Thickness
mm
Nominal Bedding Thickness
mm
Nominal Inner Sheath Thickness
mm
Nominal Outer Sheath Thickness
mm
Nominal Overall Diameter
mm
Nominal Weight kg/km
1×16 3.4 1.5 1.2 1 27.6±2 1040
1×25 3.4 1.6 1.2 1.2 29.5±2 1208
1×35 3.4 1.7 1.2 1.2 30.9±2 1386
1×50 3.4 1.7 1.3 1.2 32.3±2 1575
1×70 3.4 1.8 1.3 1.2 34.3±2 1901
1×95 3.4 1.8 1.4 1.4 36.8±2 2268
1×120 3.4 1.9 1.4 1.4 38.9±2 2741
1×150 3.4 2 1.5 1.4 40.9±2 3140
1×185 3.4 2 1.5 1.4 42.7±2 3612
1×240 3.4 2.2 1.6 1.6 46.3±2 4389
1×300 3.4 2.3 1.7 1.6 49.1±2 5177
1×400 3.4 2.4 1.7 1.6 52.2±2 6195
1×500 3.4 2.5 1.8 1.6 55.7±2 7424
1×630 3.4 2.7 1.9 1.6 60.2±2 9125
3×16 3.4 2.4 1.8 1 52.2±2 3969
3×25 3.4 2.5 1.8 1.2 55.6±2 4599
3×35 3.4 2.6 1.9 1.2 58.8±2 5292
3×50 3.4 2.7 2 1.2 61.7±2 6027
3×70 3.4 2.9 2.1 1.2 66.1±2 7245
3×95 3.4 3.1 2.2 1.4 71.2±2 8684
3×120 3.4 3.2 2.3 1.4 74.9±2 9944
3×150 3.4 3.3 2.4 1.4 78.8±2 11340
3×185 3.4 3.5 2.5 1.4 83.6±2 12989
3×240 3.4 3.7 2.7 1.6 91.4±2 15792
3×300 3.4 3.9 2.9 1.6 97.2±2 18323