UKOOA TYPE LA 600/1000V Flame Retardant
Application:
Marine cables are designed for fixed installation for power, control and lighting in both and safe areas, emergency and critical offshore applications where cable protection is required.
Standards:
BS 6883/BS 7917/UKOOA
IEC 60332-3-22 CAT. A
IEC 60332-1
IEC 60754-1 & IEC 60754-2
IEC 61034-1 & IEC 61034-2
Construction:
Conductors:Stranded class 2 or flexible class 5 tinned annealed copper conductors to BS 6360/IEC 60228.
Insulation:EPR complying with BS7655 GP4
Bedding:CSP – SW2 compound complying with BS 7655.
Armour :Tinned Phosphor Bronze Wire Braid to BS2873-PB102 (now BS EN 12166)
Outer Sheath :CSP – SW2 compound complying with BS 7655.
Dimensions and Weight:
Construction No. of cores×Cross section |
Nominal Insulation Thickness |
Nominal Thickness of Inner Sheath |
Nominal Thickness of Outer Sheath |
Nominal Overall Diameter |
Approx. Weight |
---|---|---|---|---|---|
mm² | mm | mm | mm | mm | kg/km |
1×1.0 | 0.8 | 1.1 | 1.2 | 9.5 | 150 |
1×1.5 | 0.8 | 1.1 | 1.2 | 9.8 | 170 |
1×2.5 | 0.8 | 1.1 | 1.2 | 10.2 | 190 |
1×4 | 1.0 | 1.1 | 1.2 | 11.3 | 260 |
1×6 | 1.0 | 1.1 | 1.2 | 11.8 | 340 |
1×10 | 1.0 | 1.1 | 1.2 | 13.0 | 390 |
1×16 | 1.0 | 1.1 | 1.2 | 14.2 | 480 |
1×25 | 1.2 | 1.1 | 1.2 | 16.8 | 565 |
1×35 | 1.2 | 1.1 | 1.3 | 17.9 | 740 |
1×50 | 1.4 | 1.1 | 1.4 | 19.7 | 940 |
1×70 | 1.4 | 1.0 | 1.4 | 21.9 | 1270 |
1×95 | 1.6 | 1.2 | 1.4 | 24.5 | 1500 |
1×120 | 1.6 | 1.4 | 1.6 | 26.6 | 1750 |
1×150 | 1.8 | 1.6 | 1.8 | 29.0 | 2200 |
1×185 | 2.0 | 1.8 | 2.1 | 32.6 | 2700 |
1×240 | 2.2 | 1.3 | 1.5 | 36.0 | 3400 |
1×300 | 2.4 | 1.5 | 1.7 | 39.2 | 4200 |
1×400 | 2.6 | 1.7 | 2.0 | 43.7 | 5700 |
1×500 | 2.8 | 1.2 | 1.3 | 48.1 | 7200 |
1×630 | 2.8 | 1.0 | 1.2 | 52.3 | 8840 |