UKOOA TYPE XC 600/1000V Fire Resistant
Application:
Marine cables are designed for fixed installation for power, control and lighting in both and safe areas, emergency and critical offshore applications where cable protection is required.
Standards:
BS 6883/BS 7917/UKOOA
IEC 60331-21
IEC 60332-3-22 CAT. A
IEC 60332-1
IEC 60754-1 & IEC 60754-2
IEC 61034-1 & IEC 61034-2
Construction:
Conductors:Stranded class 2 or flexible class 5 tinned annealed copper conductors to BS 6360/IEC 60228.
Fire Protection :Mica glass tape
Insulation:EPR complying with BS7655 GP4
Bedding:CSP – SW2 compound complying with BS 7655.
Armour :Tinned Phosphor Bronze Wire Braid to BS2873-PB102 (now BS EN 12166)
Outer Sheath :CSP – SW2 compound complying with BS 7655
Dimensions and Weight:
Construction No. of cores×Cross section |
Nominal Insulation Thickness |
Nominal Thickness of Inner Sheath |
Nominal Thickness of Outer Sheath |
Nominal Overall Diameter |
Approx. Weight |
---|---|---|---|---|---|
mm² | mm | mm | mm | mm | kg/km |
1×1.0 | 0.8 | 1.1 | 1.2 | 10.0 | 158 |
1×1.5 | 0.8 | 1.1 | 1.2 | 10.3 | 179 |
1×2.5 | 0.8 | 1.1 | 1.2 | 10.7 | 200 |
1×4 | 1.0 | 1.1 | 1.2 | 11.8 | 273 |
1×6 | 1.0 | 1.1 | 1.2 | 12.3 | 357 |
1×10 | 1.0 | 1.1 | 1.2 | 13.5 | 410 |
1×16 | 1.0 | 1.1 | 1.2 | 14.7 | 504 |
1×25 | 1.2 | 1.1 | 1.2 | 17.3 | 593 |
1×35 | 1.2 | 1.1 | 1.3 | 18.4 | 777 |
1×50 | 1.4 | 1.1 | 1.4 | 20.2 | 987 |
1×70 | 1.4 | 1.1 | 1.4 | 22.4 | 1333 |
1×95 | 1.6 | 1.1 | 1.5 | 25.0 | 1575 |
1×120 | 1.6 | 1.2 | 1.6 | 27.1 | 1838 |
1×150 | 1.8 | 1.2 | 1.6 | 29.5 | 2310 |
1×185 | 2.0 | 1.2 | 1.7 | 33.1 | 2835 |
1×240 | 2.2 | 1.2 | 1.8 | 36.5 | 3570 |
1×300 | 2.4 | 1.2 | 1.9 | 40.0 | 4410 |
1×400 | 2.6 | 1.2 | 1.9 | 44.2 | 5985 |
1×500 | 2.8 | 1.2 | 1.9 | 48.6 | 7560 |
1×630 | 2.8 | 1.2 | 1.9 | 52.8 | 9282 |