HOMEPRODUCTS AIRPORT CABLES

 

BMS (Building Management System)

Analog Signal Cable FFX200 05mROZ1-R/F 2G1.5

FFX200 05mROZ1-R 2G1.0 (CU/MGT+XLPE/OSCR/LSZH 2×1.0mmsq 300/500V class 2)

FFX200 05mROZ1-F 2G1.0 (CU/MGT+XLPE/OSCR/LSZH 2×1.0mmsq 300/500V class 5)

 

 

Applications:

Airport cables are multicore stranded flexible cables sheathed with thermoplastic LSZH compound. Airport cables have the ability to restrict the propagation of the flame in the event of a fire. Airport cable is especially important to slow down the spreading of the fire as the cables may pass from one area to another within a building. Applications can be found in control and power circuits, power stations, underground tunnels, lifts, escalators, and high-rise buildings.

Standards:

Basic design :BS 7629-1

Halogen Free :IEC 60754-1

No corrosive gas emission :IEC 60754-2

Minimum Smoke Emission :IEC 61034-1/2

Reduced Fire Propagation :IEC 60332-3C / NF C 32070-2.2 (C1)

Flame Retardance :IEC 60332-1 / NF C 32-070-2.1 (C2)

Fire Resistance :IEC 60331 / NF C 32070-2.3(CR1)

VOLTAGE RATING:

300/500V

Construction:

FFX200 05mROZ1-F 2G1.0 (CU/MGT+XLPE/OSCR/LSZH 2×1.0mmsq 300/500V class 5)

Conductors: Plain annealed copper wire, stranded according to EN 60228 class 2 or class 5.

Insulation: Mica glass tape covered by extruded cross-linked XLPE compound.

Cable elements: Insulated cores are twisted to form pairs.

Cabling: Pairs are cabled together.

Overall screen: Aluminum/polyester tape with copper drain wire.

Outer sheath: Thermoplastic LSZH compound.

COLOUR CODE:

Insulation Colour: According to IEC 60189-2 (other colour code on request).

Sheath Colour: Colour red (other colours on request).

Electrical PROPERTIES :

Dielectric test: 2000 V r.m.s. x 5’ (core/core)
Insulation resistance 1000 MΩ x km (at 20°C)
Short circuit temperature 250°C

Physical AND THERMAL PROPERTIES:

Temperature range during operation (fixed state): -30°C – +90°C

Temperature range during installation (mobile state): -20°C – +50°C

Minimum bending radius: 8 × Overall Diameter

CONSTRUCTION PARAMETERS:

FFX200 05mROZ1-R 2G1.5

FFX200 05mROZ1-F 2G1.5

No.of core Nominal
Cross Sectional Area
Number &
Nominal Diameter of Strands
Nominal Insulation Thickness Nominal Sheath Thickness Nominal Overall Diameter Approx. Weight
  mm2 No/mm mm mm mm kg/km
2 1.5 7/0.53 0.6 0.8 6.5 96
2 1.5 30/0.25 0.6 0.8 6.5 96