HOMEPRODUCTS AIRPORT CABLES

 

FL2XCYRY    

 

Applications:

Airport cables are used as airfield lighting equipment primary cables for the series circuit connecting the Constant Current Regulators and the isolating transformers, and between the isolating transformers.

Standards:

ENV 50213

IEC 60502-1

Construction:

FL2XCYRY

Conductor: Stranded bare copper conductor.

Inner Semi-Conductor: Extruded semi-conducting compound.

Insulation: XLPE.

Outer Semi-Conductor: Extruded semi-conducting compound.

Shield: Concentric layer of bare copper wires, counter helix of a copper tape.

Inner Sheath: PVC.

Armour: Steel wire armour.

Outer Sheath: PVC.

Technical Data:

Rated Voltage Uo/U (Um) :6/10kV

Maximum Conductor Temperature :90℃

Short Circuit Temperature :250℃

Operating Temperatures :-40℃~+90℃

Minimum Bending Radius :15×OD

Flame Retardant :Yes

Impacted Resistant :Yes

Weather Resistant :Yes

Oil Resistant :Yes

Dimensions and Weight :

Construction Nominal Insulation Thickness Nominal Shield Cross Section Nominal Sheath Thickness Nominal Overall Diameter Nominal Weight
No. ×mm² mm mm² mm mm kg/km
1×6 3.5 6 1.4 20.5 710