FL2XCYRY
Applications:
Airport cables are used as airfield lighting equipment primary cables for the series circuit connecting the Constant Current Regulators and the isolating transformers, and between the isolating transformers.
Standards:
ENV 50213
IEC 60502-1
Construction:
Conductor: Stranded bare copper conductor.
Inner Semi-Conductor: Extruded semi-conducting compound.
Insulation: XLPE.
Outer Semi-Conductor: Extruded semi-conducting compound.
Shield: Concentric layer of bare copper wires, counter helix of a copper tape.
Inner Sheath: PVC.
Armour: Steel wire armour.
Outer Sheath: PVC.
Technical Data:
Rated Voltage Uo/U (Um) :6/10kV
Maximum Conductor Temperature :90℃
Short Circuit Temperature :250℃
Operating Temperatures :-40℃~+90℃
Minimum Bending Radius :15×OD
Flame Retardant :Yes
Impacted Resistant :Yes
Weather Resistant :Yes
Oil Resistant :Yes
Dimensions and Weight :
Construction | Nominal Insulation Thickness | Nominal Shield Cross Section | Nominal Sheath Thickness | Nominal Overall Diameter | Nominal Weight |
---|---|---|---|---|---|
No. ×mm² | mm | mm² | mm | mm | kg/km |
1×6 | 3.5 | 6 | 1.4 | 20.5 | 710 |