HOMEPRODUCTS AIRPORT CABLES

 

450/750V PVC Insulated, PVC Sheathed Controlling Cables (4 core)

RE-YY (CU/PVC/PVC 300/500V Class 5)

 

 

APPLICATION:

Airprot cables are generally use for indoor installation and suitable for wet and damp areas. Generally used within industrial process manufacturing plants for communication, data and voice transmission signals and services, Also Airprot cables used for the interconnection of electrical equipment and instruments, typically in chemical or petrolchemical industry.

STANDARDS:

Basic design adapted to BS 5308 and VDE 0812

FIRE PERFORMANCE:

FlameRetardance (SingleVerticalWireTest)** EN60332-1-2; IEC60332-1-2; BSEN 60332-1-2; VDE0482-332-1; NBN C30-004 (cat.F1);NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced FirePropagation(Vertically-mountedbundledwires &cabletest)** EN60332-3-24(cat.C); IEC60332-3-24;BSEN60332-3-24;VDE0482-332-3;NBN C30-004 (cat.F2);NF C32-070-2.2(C1);CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4

Note:
Asterisk * denotes superseded standard

Asterisk ** denotes that the standard compliance is optional, depending on the oxygen index of the PVC compound and the cable design.

VOLTAGE RATING:

300/500V

CABLE CONSTRUCTION:

RE-YY (CU/PVC/PVC 300/500V Class 5)

Conductor: Plain annealed copper wire, stranded according to BS 6360 Class 5

Insulation: PVC (polyvinyl chloride), type TI1 to BS 6746

Binder Tape: PETP transparent tape

Outer Sheath: PVC Sheath, type TM 1 or type 6 to BS 6746

COLOUR CODE:

Insulation Colour as per BS 7671

Black with Arabic numbers printing in white colour

Outer sheath: Black or as order

Physical AND THERMAL PROPERTIES:

Operating Temperature: -40˚C up to + 70˚C( fixed installation)

0˚C to +50˚C(during operation )

Minimum Bending Radius: 5 x Overall Diameter

Insulation Resistance Min.: 25 Mohm/km

CONSTRUCTION PARAMETERS:

Conductor RE-YY
No.of CoreX Cross Section No./ Nominal
Diameterof
Strands
Conductor Diameter Nominal Insulation Thickness Nominal Sheath Thickness Nominal Overall Diameter Approx. Weight DcResistanceper conductor @20℃
NO.×mm2 No./mm mm mm mm mm kg/km Ω/km
4x1.0 30/0.2 1.32 0.6 0.9 8.2 92 19.5

Electrical PROPERTIES:

Conductor Operating Temperature : 90°C

Ambient Temperature : 30°C