2491X to BS 6004 Cables
450/750V PVC Insulated, PVC Sheathed Controlling Cables (2 core & 6 core)
FGD200 07VV-F (CU/PVC/PVC 450/750V Class 5)
APPLICATION:
Airprot cables are multicore stranded flexible cables sheathed with thermoplastic PVC compound. The cables are designed specially for fire alarm systems where the integrity of the electrical circuit is critical in maintaining power supply. Applications can be found in emergency lightings, control and power circuits, power stations, fire alarm systems, underground.
STANDARDS:
Basic design to BS 6004, BS6500
FIRE PERFORMANCE :
FlameRetardance (SingleVerticalWireTest)** | EN60332-1-2; IEC60332-1-2; BSEN 60332-1-2; VDE0482-332-1; NBN C30-004 (cat.F1);NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* |
---|---|
Reduced FirePropagation(Vertically-mountedbundledwires &cabletest)** | EN60332-3-24 (cat.C); IEC60332-3-24;BSEN60332-3-24;VDE0482-332-3;NBN C30-004 (cat.F2);NF C32-070-2.2(C1);CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 |
Note:
Asterisk * denotes superseded standard
Asterisk ** denotes that the standard compliance is optional, depending on the oxygen index of the PVC compound and the cable design.
VOLTAGE RATING:
450/750V
CABLE CONSTRUCTION:
Conductor: Plain annealed copper wire, stranded according to BS 6360 Class 5
Insulation: PVC insulation type TI1 to BS 7655
Filler, binder (if any): PP, PET
Outer Sheath: PVC sheath type T6 to BS 7655 COLOUR CODE
Insulation Colour as per BS7671
with earth conductor | without earth conductor | |
---|---|---|
2Cores | - | Brown,Blue |
3Cores | Yellow/Green,Brown,Blue | Brown,Gray,Black |
4Cores | Yellow/Green,Brown,Gray,Black | Brown,Gray,Black,Blue |
5Cores | Yellow/Green,Brown,Gray,Black,Blue | Brown,Gray,Black,Blue,Black |
above 5 Cores | Yellow/Green,BlackNumbers | Black Numbers |
Outer sheath: Black or as order
Physical AND THERMAL PROPERTIES:
Operating temperature: -15º C to +70º C
Short circuit temperature: +160º C
Minimum bending radius: 4x Overall Diameter
Insulation resistance: 20 MΩxkm
CONSTRUCTION PARAMETERS :
Conductor | fGD20007VV-f | ||||||
---|---|---|---|---|---|---|---|
No.of CoreXCross Section |
No./ Nomina lDiameter of Strands |
Conductor Diameter |
Nominal Insulation Thickness |
Nominal Sheath Thickness |
Nominal Overall Diameter |
Max.DC resistance ofconductor @20°C | Approx. Weight |
Noxmm2 | No./mm | mm | mm | mm | mm | Ω/km | kg/km |
2x1.0 | 32/0.20 | 1.32 | 0.6 | 0.9 | 7.0 | 18.1 | 66 |
6x1.0 | 32/0.20 | 1.32 | 0.6 | 1.0 | 10..2 | 18.1 | 159 |
Electrical PROPERTIES:
Conductor Operating Temperature : 90°C
Ambient Temperature : 30°C
Currnt-Carrying Capacities (Amp) :
Conductor cross- sectional area | Reference Method4 (enclosed inconduit in thermally insulating walletc) |
Reference Method3 (enclosed inconduit ona wallorin trunkingetc) |
Reference Method1 (clipped direct) |
Reference Method11 (onaperforated cabletray, horizontalor vertical) |
Reference Method 12 (freeair) |
||
---|---|---|---|---|---|---|---|
Horizontal flat spaced |
Vertical flat spaced |
Trefoil |
2cables, single- phase a.c.ord.c. |
3 or cables, 3-phasea.c. |
2 cables, single- phase a.c.ord.c |
3 or 4cables, 3-phasea.c. | 2cables, single- phase a.c.or d.c. flat and touching |
3 or 4cables, 3-phase a.c. flat and touching or trefoil |
2cables, single- phase a.c.or d.c.orflat and touching |
3 or 4cables, 3-phase a.c. flat and touching or trefoil |
2cables, single- phase a.c.ord.c.or 3cables three phase |
2cables, single- phase a.c.ord.c .or 3cables three phase |
3cables, trefoil 3-phasea.c. |
|
---|---|---|---|---|---|---|---|---|---|---|---|
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 |
mm2 | A | A | A | A | A | A | A | A | A | A | A |
1.0 | 13 | - | - | - | 15 | - | - | - | - | - | - |
Nominal Cross Section Area |
2cables d.c. | 2cables, single- phasea.c. |
3or 4cables, 3-phase a.c. |
|||
---|---|---|---|---|---|---|
Ref.Methods3 and 4 (enclosed inconduitetc ,inoron a wall) |
Ref.Methods1 and11 (clipped director ontray stouching) |
Ref. Methods3 and 4 (enclosed inconduitetc, inoron a wall) |
Ref.Methods1, | Ref. Methods 1and11 |
||
11 and12 (intrefoil) | (Flat and touching) | |||||
1 | 2 | 3 | 4 | 5 | 6 | 7 |
mm2 | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m |
1.0 | 46 | 46 | - | - | - | - |