HOMEPRODUCTS AIRPORT CABLES

 

2491X to BS 6004 Cables

450/750V PVC Insulated, PVC Sheathed Power Cables (2 core & 3 core)

FGD200 07VV-F (CU/PVC/PVC 450/750V Class 5)

 

 

APPLICATION :

Airprot cables are mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals, and high-rise buildings. The cables can be offered with the ability to restrict the propagation of the flame in the event of a fire.

STANDARDS :

Basic design to BS 6004, BS6500

FIRE PERFORMANCE :

FlameRetardance (SingleVerticalWireTest)** EN60332-1-2; IEC60332-1-2; BSEN 60332-1-2; VDE0482-332-1; NBN C30-004 (cat.F1);NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced FirePropagation(Vertically-mountedbundledwires &cabletest)** EN60332-3-24 (cat.C); IEC60332-3-24;BSEN60332-3-24;VDE0482-332-3;NBN C30-004 (cat.F2);NF C32-070-2.2(C1);CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4

Note:

Asterisk * denotes superseded standard

Asterisk ** denotes that the standard compliance is optional, depending on the oxygen index of the PVC compound and the cable design.

VOLTAGE RATING :

450/750V

CABLE CONSTRUCTION :

FGD200 07VV-F (CU/PVC/PVC 450/750V Class 5)

Conductor: Plain annealed copper wire, stranded according to BS 6360 Class 5

Insulation: PVC insulation type TI1 to BS 7655

Filler, binder (if any): PP, PET

Outer Sheath: PVC sheath type T6 to BS 7655

COLOUR CODE :

Insulation Colour as per BS7671

  withearth conductor withoutearth conductor
2Cores - Brown,Blue
3Cores Yellow/Green,Brown,Blue Brown,Gray,Black
4Cores Yellow/Green,Brown,Gray,Black Brown,Gray,Black,Blue
5Cores Yellow/Green,Brown,Gray,Black,Blue Brown,Gray,Black,Blue,Black
above 5 Cores Yellow/Green,BlackNumbers Black Numbers

Outer sheath: Black or as order

Physical AND THERMAL PROPERTIES :

Operating temperature: -15º C to +70º C

Short circuit temperature: +160º C

Minimum bending radius: 4x Overall Diameter

Insulation resistance: 20 MΩxkm

CONSTRUCTION PARAMETERS :

Conductor fGD20007VV-f
  No.of
CoreXCross
Section
    No./
Nominal
Diameterof
Strands
   Conductor
Diameter
    Nominal
Insulation Thickness
    Nominal
Sheath Thickness
    Nominal
Overall Diameter
  Max.DC resistance ofconductor @20°C    Approx. Weight
Noxmm2 No./mm mm mm mm mm Ω/km kg/km

2x1.5

30/0.25

1.6 0.7 0.9 9.3

12.1

108

3x2.5

50/0.25

2.0 0.8 1.2

10.8

7.41

179

Electrical PROPERTIES :

Conductor Operating Temperature : 90°C

Ambient Temperature : 30°C

Current-Carrying Capacities (Amp) :

    Conductor
cross- sectional area
    Reference Method4
(enclosed inconduit in thermally
insulating
walletc)
Reference
Method3 (enclosed inconduit ona wallorin trunkingetc)
     Reference
Method1
(clipped direct)
  Reference
Method11
(onaperforated cabletray,
horizontalorvertical)
Reference
Method 12
(freeair)
  Horizontal
flat spaced
  Vertical
flat spaced
   Trefoil

2cables, single- phase a.c.ord.c. 3 or 4cables, 3-phasea.c. 2cables, single- phase a.c.ord.c 3 or 4cables, 3-phasea.c. 2cables, single- phase
a.c.or d.c. flat andtouching
3 or 4cables, 3-phase
a.c. flat
andtouching or trefoil
2
cables, single- phase
a.c.or
d.c.orflat and touching
3 or 4cables, 3-phase
a.c. flat
andtouching or trefoil
2cables, single- phase
a.c.ord.c.or 3cablesthree phase
2cables, single- phase
a.c.ord.c.or 3
cables three phase
3 cables, trefoil 3- phasea.c.
1 2 3 4 5 6 7 8 9 10 11 12

mm2

A A A A A A A A A A A
1.5 18 17

22

19 25 23 - - - - -
2.5 24 23

30

26 34 31 - - - - -

Voltage Drop(PerAmp PerMeter)

Nominal
CrossSection Area
2cables d.c. 2cables,single-phasea.c. 3or 4cables,3-phase a.c.
Ref.Methods3
and 4 (enclosed
inconduitetc,
inoron a wall)
Ref.Methods1 and11(clipped
director ontray
stouching)
Ref.Methods3
and 4 (enclosed
inconduitetc
,inoron a wall)
Ref.Methods1, Ref.Methods1and11
11 and12 (intrefoil) (Flat and touching)
1 2 3 4 5 6 7
mm2 mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m mV/A/m
1.5 31 31 27 27 27 27
2.5 19 19 16 16 16 16