CPMS (Car Park Management System)
Talk-back Cable FFX200 05mROZ1-R/F 2G1.0
FFX200 05mROZ1-R 2G1.0 (CU/MGT+XLPE/OSCR/LSZH 2×1.0mmsq 300/500V class 2)
FFX200 05mROZ1-F 2G1.0 (CU/MGT+XLPE/OSCR/LSZH 2×1.0mmsq 300/500V class 5)
Applications:
Airprot cables are single pair stranded flexible cables sheathed with thermoplastic LSZH compound.Airprot cables have the ability to restrict the propagation of the flame in the event of a fire.Airprot cable is especially important to slow down the spreading of the fire as the cables may pass from one area to another within a building. Applications can be found in control and power circuits, power stations, underground tunnels, lifts, escalators, and high-rise buildings.
Standards:
Basic design :BS 7629-1
Halogen Free :IEC 60754-1
No corrosive gas emission :IEC 60754-2
Minimum Smoke Emission :IEC 61034-1/2
Reduced Fire Propagation :IEC 60332-3C / NF C 32070-2.2 (C1)
Flame Retardance :IEC 60332-1 / NF C 32-070-2.1 (C2)
Fire Resistance :IEC 60331 / NF C 32070-2.3(CR1)
VOLTAGE RATING:
300/500V
Construction:
Conductors: Plain annealed copper wire, stranded according to EN 60228 class 2 or class 5.
Insulation: Mica glass tape covered by extruded cross-linked XLPE compound.
Cable elements: Insulated cores are twisted to form pairs.
Cabling: Pairs are cabled together.
Overall screen: Aluminum/polyester tape with copper drain wire.
Outer sheath: Thermoplastic LSZH compound.
COLOUR CODE:
Insulation Colour: According to IEC 60189-2 (other colour code on request).
Sheath Colour: Colour red (other colours on request).
Electrical PROPERTIES :
Dielectric test: 2000 V r.m.s. x 5’ (core/core)
Insulation resistance :1000 MΩ x km (at 20°C)
Short circuit temperature :250°C
Physical AND THERMAL PROPERTIES:
Temperature range during operation (fixed state): -30°C – +90°C
Temperature range during installation (mobile state): -20°C – +50°C
Minimum bending radius: 8 × Overall Diameter
CONSTRUCTION PARAMETERS:
FFX200 05mROZ1-R 2G1.0
FFX200 05mROZ1-F 2G1.0
No.of core | Nominal Cross Sectional Area |
Number & Nominal Diameter of Strands |
Nominal Insulation Thickness | Nominal Sheath Thickness | Nominal Overall Diameter | Approx. Weight |
---|---|---|---|---|---|---|
mm2 | No/mm | mm | mm | mm | kg/km | |
2 | 1.0 | 7/0.44 | 0.6 | 0.9 | 7.2 | 64 |
2 | 1.0 | 32/0.2 | 0.6 | 0.9 | 7.2 | 64 |