Industrial Cables
Industrial Cables Multi-Core Flexible Cables
6192Y/ 6193Y to BS 6004
Application and Description:
6192Y/ 6193Y to BS 6004 cables are suitable for fixed installation in dry or damp premises on walls, boards or trays, in channels or embedded in plaster. 6192Y/ 6193Y to BS 6004 cables should be laid in conduit in conduit or trunking where mechanical protection is required.
Cable Construction:
Fine bare copper strands
Stranding to BS 6360, IEC 60228 Class 1 or 2
PVC insulation type TI1 to BS 7655
PVC sheath type T6 to BS 7655
Core Identification:
2 cores: brown and blue
3 cores: brown, black and grey
Technical Characteristics:
Working voltage: 300/500v
Test voltage: 2000 volts
Minimum bending radius: 4xOverall diameter
Operating temperature: -15º C to +70º C
Short circuit temperature: +160º C
Flame retardant: IEC 60332.1
Insulation resistance: 10 MΩxkm
Cable Parameter :
AWG (No of Strands/ Strand Diameter) | No. of Cores x Nominal Cross Sectional Area #xmm² |
Nominal thickness of insulation mm |
Nominal thickness of sheath mm |
Nominal overall dimensions | Nominal Weight kg/km | |
---|---|---|---|---|---|---|
lower limit mm |
upper limit mm |
|||||
6192Y | ||||||
17 | 2 × 1.0 | 0.6 | 0.9 | 4x6.2 | 4.7x7.4 | 53 |
16 | 2 × 1.5 | 0.7 | 0.9 | 4.4x7.0 | 5.4x8.4 | 70 |
14 | 2 × 2.5 | 0.8 | 1 | 5.2x8.4 | 6.2x9.8 | 105 |
12(7/20) | 2 × 4 | 0.8 | 1 | 6x10.4 | 7.2x11.5 | 150 |
10(7/18) | 2 × 6 | 0.8 | 1.1 | 6.8x11.5 | 8.0x13.0 | 205 |
8(7/16) | 2 × 10 | 1 | 1.2 | 7.8x15.1 | 9.6x16 | 325 |
6(7/14) | 2 × 16 | 1 | 1.3 | 9.8x17.2 | 11.0x18.5 | 465 |
6193Y | ||||||
17 | 3 × 1.0 | 0.6 | 0.9 | 4x8.4 | 4.7x9.8 | 77 |
16 | 3 × 1.5 | 0.7 | 0.9 | 4.4x9.8 | 5.4x11.5 | 100 |
14 | 3 × 2.5 | 0.8 | 1 | 5.2x11.5 | 6.2x13.5 | 150 |
12(7/20) | 3 × 4 | 0.8 | 1.1 | 6x14.8 | 7.4x16.5 | 230 |
10(7/18) | 3 × 6 | 0.8 | 1.1 | 6.8x16.5 | 8.0x18.0 | 300 |
8(7/16) | 3 × 10 | 1 | 1.2 | 7.8x21.0 | 9.6x22.5 | 485 |
6(7/14) | 3 × 16 | 1 | 1.3 | 9.8x24.8 | 11.0x26.5 | 700 |