HOMEPRODUCTS PORTUGUESE STANDARD CABLE

 

Industrial Cables

Industrial Cables Multi-Core Flexible Cables

6241B/6242B/ 6243B to BS 7211

 

 

 

Application and Description:

6241B/6242B/ 6243B to BS 7211 cables are suitable for fixed installation particularly for situations in which low emission smoke and domestic wiring cable for the surface wiring of sockets and lighting where fire, smoke emission and toxic fumes create a potential threat to life and equipment. Can be installed in fixed installations in dry or damp premises on walls, boards or trays, in channels or embedded in plaster. Suitable for laying in conduit or trunking where mechanical protection is required.

Cable Construction:

Fine bare copper strands

Stranding to IEC 60228 Class 1 or 2

Thermosetting core insulation type EI5 or GP 8

The core or cores shall be laid parallel with the uninsulated circuit protective conductor For twin cores, the protective conductor centrally placed between cores in same plane For 3 cores, the protective conductor centrally placed between black and grey cores in same plane LSOH sheath, type LTS 2, white

6241B/6242B/ 6243B to BS 7211

6241B

Industrial Cables 6241B/6242B/ 6243B to BS 7211

6242B

Industrial Cables 6241B/6242B/ 6243B to BS 7211

6243B

Core Identification:

2 cores: brown and blue, or, for 2 × 1.0 and 2 × 1.5 cables, brown and brown

3 cores: brown, black (centre core) and grey

Technical Characteristics:

Working voltage: 300/500v

Test voltage: 2000 volts

Flexing bending radius: 15xOverall diameter

Static bending radius: 10xOverall diameter

Flexing temperature: +5º C to +90º C

Short circuit temperature: +250º C

Insulation resistance: 10 MΩxkm

Halogen free acc. to EN 50267-2-1 / IEC 60754-1

Smoke density acc. to EN 50268-2 / IEC 61034-2

Corrosivity of gases acc. to EN 50267-2-2, IEC 60754-2

Flame retardancy acc. to EN 50265-2-1, IEC 60332-1

Cable Parameter :

AWG (No of Strands/ Strand Diameter) No. of Cores x Nominal Cross Sectional Area
#xmm²
Nominal thickness of insulation
mm
Nominal thickness of sheath
mm
Nominal overall dimensions Circuit protective conductor AWG Nominal Weight kg/km
lower limit
mm
upper limit
mm
6241B
17 1 × 1.0 0.7 0.9 4.1 × 5.2 5.0 × 6.3 17 45
16 1 × 1.5 0.7 0.9 4.4 × 5.4 5.3 × 6.6 17 55
6242B
17 2 × 1.0 0.7 0.9 4.1 × 7.6 5.0 × 9.1 17 68
17(7/26) 2 × 1.0 0.7 0.9 4.2 × 7.8 5.1 × 9.4 17 73
16 2 × 1.5 0.7 0.9 4.4 × 8.1 5.3 × 9.7 17 85
16(7/24) 2 × 1.5 0.7 0.9 4.5 × 8.3 5.4 × 10 17 90
14 2 × 2.5 0.7 1.0 4.9 × 9.3 6 × 11.2 16 120
14(7/22) 2 × 2.5 0.7 1.0 5.0 × 9.5 6.1 × 11.4 16 125
12(7/20) 2 × 4 0.7 1.0 5.5 × 10.4 6.7 × 12.6 16 175
10(7/18) 2 × 6 0.7 1.1 6.2 × 12.0 7.5 × 14.6 14 240
8(7/16) 2 × 10 0.7 1.2 7.3 × 14.5 8.8 × 17.6 12(7/20) 390
6(7/14) 2 × 16 0.7 1.3 8.4 × 17.0 10.1 × 20.5 10(7/18) 560
6243B
17 3 × 1.0 0.7 0.9 4.1 × 10 5.1 × 12.1 17 91
16 3 × 1.5 0.7 0.9 4.4 × 10.7 5.3 × 12.9 17 115
14 3 × 2.5 0.7 1.0 4.9 × 12.0 6 × 14.6 17 170
12(7/20) 3 × 4 0.7 1.0 5.5 × 14 6.7 × 16.9 16 196
10(7/18) 3 × 6 0.7 1.1 6.2 × 16.2 7.5 × 19.5 14 291
8(7/16) 3 × 10 0.7 1.2 7.3 × 19.5 8.8 × 23.6 12(7/20) 440
6(7/14) 3 × 16 0.7 1.3 8.4 × 22.8 10.1 × 27.6 10(7/18) 670