HOMEPRODUCTSBRITISH STANDARD INDUSTRIAL CABLE

 

Industrial Cables-British Standard

6181X/6182X/6183X/6184X/6185X to BS 7889

 

 

 

Application and Description :

6181X/6182X/6183X/6184X/6185X to BS 7889 cables are designed for surface wiring where there is little risk of mechanical damage and are suitable for use in electrical installations such as power and lighting.

Cable Construction:

6181X/6182X/6183X/6184X/6185X to BS 78896181X/6182X/6183X/6184X/6185X to BS 7889

    Bare copper conductor

    Stranding to BS 6360 CL-2 or IEC 60228 CL-2

    XLPE GP8 insulation

    Inner covering (optional)

    PVC sheath Type 9 to BS7655-4.2

Core Identification:

1-core: brown or blue;

2-core: brown and blue;

core: brown, black and grey;or green/yellow,brown and blue

core: blue, brown, black and grey; or green/yellow, brown, black and grey

  • 5-core: greenlyellow, blue, brown, black and grey

  • Technical Characteristics:

  • Working voltage:  600/1000V

    Minimum bending radius: OD<25 mm : 4xoverall diameter,

  • Operating temperature: -15º C to +90º C

    Insulation resistance: 10 MΩxkm

    Flame retardant: IEC 60332.1

  • Cable Parameter:

    Nominal
    Cross
    Sectional
    Area
    mm²
    Nominal
    Thickness
    of
    Insulation
    mm
    Nominal
    Thickness
    of Inner
    Covering
    mm
    Nominal Thickness of Sheath
    mm
    Nominal
    Cross
    Sectional
    Area
    mm²
    Nominal
    Thickness
    of
    Insulation
    mm
    Nominal
    Thickness
    of Inner
    Covering
    mm
    Nominal Thickness of Sheath
    mm
    6181X 6182X
    1.5 0.7 0.4 1.4 1.5 0.7 0.4 1.8
    2.5 0.7 0.4 1.4 2.5 0.7 0.4 1.8
    4 0.7 0.4 1.4 4 0.7 0.4 1.8
    6 0.7 0.4 1.4 6 0.7 0.4 1.8
    10 0.7 0.4 1.4 10 0.7 0.6 1.8
    16 0.7 0.4 1.4 16 0.7 0.6 1.8
    25 0.9 0.4 1.4 25 0.9 0.8 1.8
    35 0.9 0.4 1.4 35 0.9 0.8 1.8
    50 1.0 0.6 1.4 50 1.0 1.0 1.8
    70 1.1 0.6 1.4 70 1.1 1.0 1.8
    95 1.1 0.6 1.5 95 1.1 1.2 1.9
    120 1.2 0.8 1.5 120 1.2 1.2 2.0
    150 1.4 0.8 1.6 25 * 0.9 0.6 1.8
    185 1.6 0.8 1.6 35 * 0.9 0.6 1.8
    240 1.7 1.0 1.7 50 * 1.0 0.8 1.8
    300 1.8 1.0 1.8 70 * 1.1 0.8 1.8
    400 2.0 1.2 1.9 95 * 1.1 1.0 1.9
    500 2.2 1.2 2.0 120 * 1.2 1.0 2.0
    630 2.4 1.4 2.2 *Shaped stranded conductor
    800 2.6 1.6 2.3
    1000 2.8 1.6 2.4
    Nominal
    Cross
    Sectional
    Area
    mm²
    Nominal
    Thickness
    of
    Insulation
    mm
    Nominal
    Thickness
    of Inner
    Covering
    mm
    Nominal Thickness of Sheath
    mm
    Nominal
    Cross
    Sectional
    Area
    mm²
    Nominal
    Thickness
    of
    Insulation
    mm
    Nominal
    Thickness
    of Inner
    Covering
    mm
    Nominal Thickness of Sheath
    mm
    6183X 6184X
    1.5 0.7 0.4 1.8 1.5 0.7 0.4 1.8
    2.5 0.7 0.4 1.8 2.5 0.7 0.4 1.8
    4 0.7 0.4 1.8 4 0.7 0.4 1.8
    6 0.7 0.4 1.8 6 0.7 0.6 1.8
    10 0.7 0.6 1.8 10 0.7 0.6 1.8
    16 0.7 0.6 1.8 16 0.7 0.6 1.8
    25 0.9 0.8 1.8 25 0.9 0.8 1.8
    35 0.9 0.8 1.8 35 0.9 1.0 1.8
    50 1.0 1.0 1.8 50 1.0 1.0 1.8
    70 1.1 1.2 1.9 70 1.1 1.2 2.0
    95 1.1 1.2 2.0 95 1.1 1.2 2.1
    120 1.2 1.2 2.1 120 1.2 1.2 2.3
    25 * 0.9 0.6 1.8 25 * 0.9 0.8 1.8
    35 * 0.9 0.8 1.8 35 * 0.9 0.8 1.8
    50 * 1.0 0.8 1.8 50 * 1.0 1.0 1.8
    70 * 1.1 1.0 1.9 70 * 1.1 1.2 2.0
    95 * 1.1 1.2 2.0 95 * 1.1 1.2 2.1
    120 * 1.2 1.2 2.1 120 * 1.2 1.2 2.3
    6185X
    1.5 0.7 0.4 1.8 25 0.9 1.0 1.8
    2.5 0.7 0.4 1.8 35 0.9 1.0 1.8
    4 0.7 0.6 1.8 50 1.0 1.2 1.9
    6 0.7 0.6 1.8 70 1.1 1.2 2.1
    10 0.7 0.6 1.8 95 1.1 1.4 2.2
    16 0.7 0.8 1.8 120 1.2 1.4 2.4

    *Shaped stranded conductor