Home
Chi siamo
Prodotti
Scaricare
Biblioteca tecnica
Contatto
Richiesta
Mappa del sito 
Collegamenti
 

Allarme & Cavo Audio & Elettronico

Cavo di Equivalente di Belden

Cavo coassiale

Cavo di Controllo

Cavo Fibra Ottica

Cavo Flessibile

Cavo strumentazione

Cavi LAN
Cavo Energia
Cavo Ferroviario

Robotic

Cavo per Materiale Rotabile
Cavo di gomma
Cavo di Sicurezza

Cavo Telefonico

Aeroporto Cavi

Bus Cavi

Serracavi

Data Cable

Calore di rilevamento Cavi
Cavi ad alta temperatura
Cavi autostrada
Marine, OIL,GAS & Petrochemical Cables
Cavi Speciali
Cavi a spirale
Termocoppia Cavi
Mining Cables
Industrial Cables
Undersea Cables
Military Cables
Marine Cables
Hoop-Up Wire
Other Cables
     
  indoor tight buffer fiber optic cable  
Indoor Used Tight Buffered Fiber
Optical Cable
outdoor multi loose tube fiber optic cable
Outdoor Used Multi Loose Tube
Fiber Optical Cable
 
  Marine Cable  

Marine Cable

P4 or P4/P11 RFOU/TFOU 8.7/15KV

Applications :

  • These cables are flame retardant, low smoke, halogen free and mud resistant, used for fixed installation for medium voltage power.

Standards :

  • IEC 60092-353 IEC 60092-351
    IEC 60092-359 IEC 60332-1
    IEC 60332-3-22 IEC 60754-1,2
    IEC 61034-1,2 NEK 606:2004
 

 

Construction :

  • Conductors : Circular tinned annealed stranded copper to IEC 60228 class 2.
  • Conductor Screen : Semi conducting material.
  • Insulation : Halogen-free EPR. XLPE can be offered as an option (for TFOU cable).
  • Insulation Screen : Semi conducting material and tinned copper wire braid.
  • Bedding : Halogen free compound.
  • Armour : Tinned copper wire braid.
  • Outer Sheath :Halogen free thermosetting compound, SHF2 (for TYPE P4), or halogen free mud resistant thermosetting compound, SHF MUD (for TYPE P4/P11), coloured red.

Electrical Characteristics :

  • Nominal Cross Section Area mm² 25 35 50 70 95 120
    Nominal Conductor Diameter mm 6.5 7.4 8.7 10.3 12.2 13.8
    Maximum DC Resistant@20℃ Ω/km 0.734 0.529 0.391 0.27 0.195 0.154
    Continuous Current Rating@45℃1 Core A 127 157 196 242 293 339
    Continuous Current Rating@45℃3 Core A 89 110 137 169 205 237
    Short Circuit Current 1s A 3580 5010 7150 10020 13590 17170
    Operating Voltage KV 8.7/15 8.7/15 8.7/15 8.7/15 8.7/15 8.7/15
  • Nominal Cross Section Area mm² 150 185 240 300 400 500 630
    Nominal Conductor Diameter mm 15.1 17.0 19.6 21.9 24.5 27.5 32.3
    Maximum DC Resistant@20℃ Ω/km 0.126 0.1 0.0762 0.0607 0.0475 0.0369 0.0286
    Continuous Current Rating@45℃1 Core A 389 444 522 601 690 780 890
    Continuous Current Rating@45℃3 Core A 272 311 365 421 483 546 623
    Short Circuit Current 1s A 21460 26470 34340 42930 57230 71540 90140
    Operating Voltage KV 8.7/15 8.7/15 8.7/15 8.7/15 8.7/15 8.7/15 8.7/15

Ambient Temperature Correction Factors :

  • Ambient Temperature Correction Factors 35 40 45 50 55 60 65 70 75 80
    Rating Factor 1.1 1.05 1.0 0.94 0.88 0.82 0.74 0.67 0.58 0.47

Mechanical and Thermal Properties :

  • Bending Radius :15×OD (during installation); 9×OD (fixed installed).
  • Temperature Range : -20℃ ~ +90℃.

Dimensions and Weight :

Construction No. of cores×Cross section
(mm²)
Nominal Insulation Thickness
mm
Nominal Sheath Thickness
mm
Nominal Overall Diameter
mm
Nominal Weight
kg/km
Inner Outer
1×25 4.5 1.6 1.2 28.4 1305
1×35 4.5 1.6 1.3 29.3 1430
1×50 4.5 1.7 1.3 30.7 1620
1×70 4.5 1.8 1.3 32.4 1900
1×95 4.5 1.8 1.4 34.4 2250
1×120 4.5 1.9 1.5 36.6 2625
1×150 4.5 2.0 1.5 38.1 2940
1×185 4.5 2.0 1.5 40.6 3545
1×240 4.5 2.1 1.6 43.4 4220
1×300 4.5 2.2 1.7 46.3 5070
1×400 4.5 2.4 1.8 50.2 5760
1×500 4.5 2.5 1.8 53.6 6880
1×630 4.5 2.6 1.9 57.9 8460
3×25 4.5 2.6 1.9 55.3 4725
3×35 4.5 2.7 2.0 57.5 5215
3×50 4.5 2.8 2.0 60.6 5960
3×70 4.5 2.9 2.1 64.4 7035
3×95 4.5 3.1 2.2 68.7 8370
3×120 4.5 3.2 2.3 72.7 9745
3×150 4.5 3.4 2.4 76.8 11140
3×185 4.5 3.6 2.6 84.2 13490
3×240 4.5 3.8 2.7 90.6 15860
3×300 4.5 4.0 2.9 96.6 18320