BS 6622 Single Core Armoured 6.6kV XLPE Stranded Aluminium Conductor
Edilizia
Size mmsq
Minimum Average Thickness of Insulation mm
Nominal Area of Copper Tape Screen mm sq
Nominal Thickness of Bedding
Nominal number and diameter of armoured wires no./ mm
Nominal Thickness of Sheath mm
Nominal Overall Diameter mm
70
2.5
16.8
1.2
38/1.6
1.8
27.5
95
18.5
41/1.6
1.9
29.4
120
20
44/1.6
30.9
150
21.3
46/1.6
2.0
32.4
185
23.1
40/2.0
35.0
240
2.6
25.5
43/2.0
2.1
37.6
300
2.8
28.3
47/2.0
2.2
40.8
400
3
31.4
51/2.0
2.3
44.1
500
3.2
34.7
1.3
46/2.5
49.0
630
38.6
1.4
50/2.5
53.3
Installation
Size
mmsq
Approximate Cable Weight kg/m
Nominal Drum Length m
Minimum Bending Radius mm
Nominal Internal Diameter of Ducts mm
1.0
1000
450
100
1.5
1.7
550
600
2.4
650
700
3.4
750
4.1
800
Performance Elettrica
Maximum DC resistance of conductor at 20 ℃ uohms/m
Maximum AC resistance of conductor at 90 ℃ uohms/m
Reactance at 50Hz uohms/m
Impedance at 50Hz uohms/m
Maximum Capacitace PF/m
Maximum charging current at normal voltage and frequency mA/m
443
568
125
582
371
0.45
320
410
119
427
417
0.50
253
325
114
344
459
0.55
206
265
111
288
494
0.59
164
211
109
238
543
0.65
161
105
193
583
0.70
130
103
167
602
0.72
77.8
102
99.9
143
627
0.75
60.5
81.0
99.2
129
654
0.79
46.9
64.0
95.5
116
737
0.87
Ratings
Current Ratings
Short circuit ratings
Laid in ground Amps
Drawn into ducts Amps
Laid in air Amps
One second short circuit rating of conductor KA
One second short circuit rating of copper per core Ka
210
6.3
-
250
245
295
8.5
280
275
335
11.0
Typically
315
380
13.5
Less
355
435
17.0
Then
405
510
22.3
1kA
455
420
580
28.0
670
36.6
570
770
46.2
640
880
58.3