Bus Cables
Indoor 3 pairs 2 core 0.22mm2 Halogen Free Interbus Cables
Application: The Interbus cable is used as
a standard transfer medium. It can replaces the expensive parallel
cabling for the different signal types in the lower levels of automation
technique. Interbus Cables can provide an inexpensive way for automation industry.
Conductor: Bare Copper (AWG 24/7)
Insulation: PE
Conductor Colour: White/Brown, Green/Red, Yellow/Green
Stranding: Double Conductor
Shielding: Polyester foil over stranded bundle
Total Shielding: Bare Copper Braid
Sheath/Jacket: PE
Colour: Pastel Turquoise
Outer Cable Diameter: 7.0 mm ± 0.3 mm
Test Voltage: 1.0 kV
Attenuation:
256 kHz < 1.5 dB/100m
772 kHz < 2.4 dB/100m
1 MHz < 2.7 dB/100m
4 MHz < 5.2 dB/100m
10 MHz < 8.4 dB/100m
16 MHz < 11.2 dB/100m
20 MHz < 11.9 dB/100m
Operating temperature: - 25 °C to +60°C
Standards: Interbus Specification 2.0, IEC 61158
UL Style: UL Style 2571
Size (Type) |
Characteristic Impedance |
Conductor Resistance |
Insulation Resistance |
Mutual Capacitance |
Min. Bending Radius |
Caloric Load, approx. value |
Weight |
3 X 2 X 0.22mm2 |
100 Ohm ± 15 Ohm |
96.0 Ohm/km |
1.0 GOhm x km Min. |
50.0 nF/km Nom. |
110.0 mm |
1.10MJ/m |
Approx. 67.0 kg/km |
|