TUNNEL CABLES

TUNNEL CABLES

2XSEYQY

Application

These cables are used for the connection of mobile operating equipments. In mines and underground

excavations with hazardous environments, in stationary operation, e.g.highvoltage transformers in mining and

tunneling. It can be used also for powering main pannels and switchboards in tunneling applications.

STANDARDS

construction

DIN VDE 0250-605 & IEC 60502-2

General Requirements

DIN VDE 0250-1

Guide Use

DIN VDE 0298-3

Electrical Tests

DIN VDE 0472-501, 503, 508

Non-Electrical Tests

DIN VDE 0472-401. 402,602,303, 615

Under Fire Condition Tests

DIN VDE 0472-803, 804

Flame Retardant

VDE 0482-332-1-2,DIN EN 60332-1-2,IEC 60332-1

CABLE CONSTRUCTION

conductor

Circular Stranded Plain Annealed Copper Conductor (class2 acc. to IEC 60228)

Insulation

XLPE Insulation

Electrical Field
Control

Extruded inner and outer rubber semiconductive layer

Core Identification

Natural coloring with black semiconductive layer

Screen

Copper tapes applied over each main core

Lay Up

3-Screened Cores will be laid up in concentrically

Bedding

PVC filler

Armour

Galvanized Steel Wire Braid (CSWB) Min90%

Outer Sheath

5GM5 Type elastomer compound. Red

Technical Characteristics

Rated Voltage

6 / 10 KV

AC Test Voltage

17 KV

Max.Permissible Operating Voltage AC

6.9 / 12 KV

Max.Permissible Operating Voltage DC

9 / 18 KV

Min Bending Radius

Acc. to DIN VDE 0298 part 3

Current Carrying Capacity

According to DIN VDE0298, Part 4

Working Temperature

Fixed

-25°C - +80°C

Mobile

+5°C - +80°C

Max.Tensile Load Of cable

15N/mm²

max.torsion

25°/m

Dimensions And Weight

Cross Section (mm²)

Overall Diameter
min-max (mm)

max.Dc Resistance (20°C) (Ω/km)

Appro. Weight (kg/km)

3x25/16

45.0-49.6

0.727

3650

3x35/16

47.7-52.8

0.524

4200

3x50/16

50.6-56.0

0.387

4960

3x70/16

54.5-60.2

0.268

6030

3x95/16

58.8-65.0

0.193

7300

3x120/16

62.0-68.5

0.153

8410