Coil End Lead to BS6195 Type 4
CONSTRUCTION :
Chef d'orchestre:Flexible Tinned Copper to BS6360
Isolation:Ethylene Propylene Rubber E.P.R ; Type FR1 (Voltage Categories A & C) & Type FR2 (Voltage Categories D & E) to BS 7655.
Gaine:Chlorosulphonated Polyethylene C.S.P. HOFR Black. To BS 6899
APPLICATION :
This range of Cables is designed as power leads for permanent connecton to coil winding motors, panel wiring and electrical machinery. They are able to withstand high temperature and immersion in varnish. Other applications include vehicle wiring. T he HOFR sheath resists oil and varnish and the stranding is designed as a compromise between flexibility and positional stability. Also suitable as an alternative to tri-rated and bi-rated cable in certain applications
TECHNICAL DATA :
Tension Catégories
A 300/500V
C 600/1000V
D 1900/3300V
E 3800/6600V
F 6350/11000V
Gamme de températures de fonctionnement: -20oC to +70oC
Rayon de courbure: Up to 25mm2 = 6 x overall diameter
Above 25mm2 = 8 x overall diameter
SHEATH COLOUR :
0.5-10mm2: Red-Black
10mm2 above: Black only.
RELEVANT STANDARDS :
Cable in accordance with BS6195
Insulation & Sheath to BS6899
OPTIONS
Coiled end lead is also manufactured to BS6899 Type 5 - Silicon insulation 180oC Operating Temperature.
Catégorie Tension |
Maximum d'essai des appareils de tension (ACrms) |
Tension nominale Evaluation de Cable Uo/U |
A |
2.5 |
300/500V |
C |
4.0 |
600/1000V |
D |
9.5 |
1900/3300V |
E |
17 |
3800/6600V |
Taille de base et
mm sq |
Echouage (Nombre de Strand / Volet Diamètre) |
Épaisseur nominale d'isolement mm |
Diamètre nominal de l'ensemble mm pour chaque catégorie de tension |
Catégorie Tension |
Catégorie Tension |
A |
C |
D |
E |
A |
C |
D |
E |
Mm |
mm |
|
|
|
|
|
|
|
|
0.5 |
16/0.2 |
0.8 |
1.4 |
- |
- |
3.3 |
4.5 |
- |
- |
0.75 |
24/0.2 |
0.8 |
1.4 |
- |
- |
3.5 |
4.7 |
- |
- |
1.0 |
32/0.2 |
0.8 |
1.4 |
- |
- |
3.7 |
4.9 |
- |
- |
1.5 |
30/0.25 |
0.8 |
1.4 |
- |
- |
4.0 |
5.2 |
- |
- |
2.5 |
50/0.25 |
0.9 |
1.4 |
2.8 |
- |
4.6 |
5.6 |
8.5 |
- |
4.0 |
56/0.3 |
1.0 |
1.4 |
2.8 |
- |
5.4 |
6.3 |
9.1 |
- |
6.0 |
84/0.3 |
1.0 |
1.5 |
2.8 |
- |
6.5 |
7.5 |
10.3 |
- |
10 |
80/0.4 |
1.2 |
1.5 |
2.8 |
- |
7.9 |
8.5 |
11.3 |
- |
16 |
126/0.4 |
- |
1.5 |
2.8 |
5.0 |
- |
9.6 |
12.4 |
17.2 |
25 |
196/0.4 |
- |
1.6 |
2.8 |
5.0 |
- |
11.4 |
13.8 |
18.6 |
35 |
276/0.4 |
- |
1.6 |
2.8 |
5.0 |
- |
12.8 |
12.5 |
20.0 |
50 |
396/0.4 |
- |
1.7 |
2.8 |
5.0 |
- |
14.8 |
17.1 |
22.1 |
70 |
360/0.5 |
- |
1.8 |
2.8 |
5.0 |
- |
17.2 |
19.2 |
24.2 |
95 |
475/0.5 |
- |
2.0 |
3.0 |
5.0 |
- |
19.2 |
22.0 |
26.3 |
120 |
608/0.5 |
- |
2.2 |
3.0 |
5.0 |
- |
21.9 |
23.5 |
27.8 |
150 |
756/0.5 |
- |
2.3 |
3.0 |
5.0 |
- |
24.1 |
25.5 |
29.8 |
185 |
925/0.5 |
- |
2.4 |
3.0 |
5.0 |
- |
26.3 |
27.5 |
32.1 |
240 |
1221/0.5 |
- |
2.4 |
3.0 |
5.0 |
- |
28.3 |
30.6 |
35.1 |
300 |
1525/0.5 |
- |
2.6 |
3.0 |
- |
- |
33.0 |
33.8 |
- |
400 |
2013/0.5 |
- |
2.8 |
3.0 |
- |
- |
37.4 |
37.8 |
- |
630 |
2106/0.6 |
- |
- |
3.2 |
- |
- |
- |
43.5 |
- |
Les facteurs de correction
For ambient air temperatures other than 40°C, the following factors should be applied:
Température de l'air ambiant |
Facteur de correction |
1.140 |
1.100 |
1.050 |
1.000 |
0.945 |
0.900 |
0.835 |
0.775 |
0.705 |
0.603 |
0.545 |
0.445 |
Where cables are to be grouped in free air, the following factors should be applied:
No. of Cables in Group |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
Facteur de correction |
0.80 |
0.70 |
0.70 |
0.60 |
0.56 |
0.50 |
0.50 |
Ambient air temperature 40°C
Conductor operating temperature 90°C
Electrical Characteristics |
Resistance Values (ohms per kilometre)
Chef d'orchestre Domaine nominale |
Chef d'orchestre nominale Echouage |
Max. DC résistance à 20 ° C |
Max. Cotation actuelle continue
(BS6195) Types |
mm2 |
#/mm |
ohms/Km |
Amp |
0.50 |
16/0.20 |
38.2000 |
13 |
0.75 |
24/0.20 |
25.4000 |
17 |
1.00 |
32/0.20 |
19.1000 |
20 |
1.50 |
30/0.25 |
13.0000 |
26 |
2.50 |
50/0.25 |
7.8200 |
36 |
4.00 |
56/0.30 |
4.8500 |
49 |
6.00 |
84/0.30 |
3.2300 |
64 |
10.00 |
80/0.40 |
1.8500 |
90 |
16.00 |
126/0.40 |
1.1800 |
120 |
25.00 |
196/0.40 |
0.7570 |
163 |
35.00 |
276/0.40 |
0.5380 |
203 |
50.00 |
396/0.40 |
0.3750 |
267 |
70.00 |
360/0.50 |
0.2640 |
324 |
95.00 |
475/0.50 |
0.2000 |
391 |
120.00 |
608/0.50 |
0.1560 |
455 |
150.00 |
756/0.50 |
0.1260 |
525 |
185.00 |
925/0.50 |
0.1030 |
600 |
240.00 |
1121/0.50 |
0.0778 |
725 |
300.00 |
1525/0.50 |
0.0623 |
840 |
400.00 |
2013/0.50 |
0.0472 |
1010 |
630.00 |
2160/0.60 |
0.0292 |
1450 |
Chef d'orchestre Domaine nominale |
Chef d'orchestre nominale Echouage |
Max. DC résistance à 20 ° C |
Max. Cotation actuelle continue
(BS6195) Types |
mm2 |
#/mm |
ohms/Km |
Amp |
0.50 |
16/0.20 |
38.2000 |
13 |
0.75 |
24/0.20 |
25.4000 |
17 |
1.00 |
32/0.20 |
19.1000 |
20 |
1.50 |
30/0.25 |
13.0000 |
26 |
2.50 |
50/0.25 |
7.8200 |
36 |
4.00 |
56/0.30 |
4.8500 |
49 |
6.00 |
84/0.30 |
3.2300 |
64 |
10.00 |
80/0.40 |
1.8500 |
90 |
16.00 |
126/0.40 |
1.1800 |
120 |
25.00 |
196/0.40 |
0.7570 |
163 |
35.00 |
276/0.40 |
0.5380 |
203 |
50.00 |
396/0.40 |
0.3750 |
267 |
70.00 |
360/0.50 |
0.2640 |
324 |
95.00 |
475/0.50 |
0.2000 |
391 |
120.00 |
608/0.50 |
0.1560 |
455 |
150.00 |
756/0.50 |
0.1260 |
525 |
185.00 |
925/0.50 |
0.1030 |
600 |
240.00 |
1121/0.50 |
0.0778 |
725 |
300.00 |
1525/0.50 |
0.0623 |
840 |
400.00 |
2013/0.50 |
0.0472 |
1010 |
630.00 |
2160/0.60 |
0.0292 |
1450 |
|