BS 6231 Instrumentation Kabel
Anwendung :
These cables are suitable for internal wiring of appliances and switch, control, metering and instrument panels of switchgear, etc
Bau
Standards : BS 6231, UL 83, CSA C22.2, UL Flame test UL 1581/VW1 FT1 FT2
Dirigent : plain annealed
Isolierung: Flexible PVC
Temperatur-bereich: 0 o C -105 o C
Nennspannung : 0.6 / 1kV
Min. Biegeradius : 3 x Overall diameter
Isolations colours : 0.5mm² to 25 mm² Red, black, white, grey, brown, orange, yellow, blue, green, and green/yellow.
35mm² to 120 mm² Red, black and green/yellow. . Other colours available on request.
Relevant Standards :
To BS6231, UL Style 1015, 1028, 1283, 1284; CSA TEW 105 °C; UL VW -1 Vertical Flame Test
Current Ratings
The table below lists the full Thermal current ratings which will raise the Conductor temperature to 85 °C when one cable is installed in free air at an Ambient temperature of 45 °C.
These ratings are applicable for installations which ensure that the operation of the protective device is not greater than 1.45 times the continuous current carrying capacity of the cable.
Where protection is by means of semi-enclosed fuses to BS 3036 the rating must be multiplied by a factor of 0.76.
Note:Sizes 150.0mm², 185.0mm² and 240.0mm², 300.0mm² & 400mm² are classed as dual Rated and are manufactured to UL & BS 6231 only.
SIZE
mm² |
Widerstand pro 1000M von 20 ° C
OHM |
CURRENT
RATING
AMP |
Ungefähre Volt-Drop-Konstante
MV/A/M |
0.5 |
39 |
11 |
46 |
0.75 |
26 |
14 |
31 |
1 |
19.5 |
17 |
22 |
1.5 |
13.3 |
21 |
15 |
2.5 |
7.98 |
30 |
9.1 |
4 |
4.95 |
41 |
5.7 |
6 |
3.3 |
53 |
3.8 |
10 |
1.91 |
75 |
2.2 |
16 |
1.21 |
100 |
1.4 |
25 |
0.78 |
136 |
0.89 |
35 |
0.554 |
167 |
0.64 |
50 |
0.386 |
204 |
0.45 |
70 |
0.272 |
259 |
0.32 |
95 |
0.206 |
321 |
0.24 |
120 |
0.161 |
374 |
0.19 |
150 |
0.129 |
429 |
0.15 |
185 |
0.106 |
496 |
0.13 |
240 |
0.0801 |
595 |
0.092 |
300 |
0.0641 |
680 |
0.073 |
400 |
0.06 |
868 |
@70 C 0.145 |
The voltage drop figures are for one cable only. For other circuit arrangements they should be adjusted as follows:
Single-phase 50Hz ac or 2-wire dc circuit's |
x2 |
Three-phase 50Hz ac circuit's |
x1.732 |
BS 6231 Instrumentation Cables
Range & Dimensions for BS 6231 Instrumentation cables
Teil Nr. |
Size
mm² |
Strandung
mm |
Size
AWG |
UL Style
number |
Nominale
insulation
mm |
Nominalen Durchmesser insgesamt
mm |
Gewicht
kg/km |
CCL-IC-BS6231-0.50SQ |
0.5 |
16/0.20 |
22 |
1015 |
0.8 |
2.6 |
12 |
CCL-IC-BS6231-0.75SQ |
0.75 |
24/0.20 |
20 |
1015 |
0.8 |
2.8 |
15 |
CCL-IC-BS6231-1.00SQ |
1 |
32/0.20 |
18 |
1015 |
0.8 |
3 |
18 |
CCL-IC-BS6231-1.50SQ |
1.5 |
30/0.25 |
16 |
1015 |
0.9 |
3.3 |
23 |
CCL-IC-BS6231-2.50SQ |
2.5 |
50/0.25 |
14 |
1015 |
1.0 |
3.7 |
34 |
CCL-IC-BS6231-4.00SQ |
4 |
56/0.30 |
12 |
1015 |
1.0 |
4.4 |
50 |
CCL-IC-BS6231-6.00SQ |
6 |
84/0.30 |
10 |
1015 |
1.3 |
5.1 |
71 |
CCL-IC-BS6231-10.0SQ |
10 |
80/0.40 |
8 |
1028 |
1.5 |
6.9 |
123 |
CCL-IC-BS6231-16.0SQ |
16 |
126/0.40 |
6 |
1283 |
1.5 |
8.6 |
209 |
CCL-IC-BS6231-25.0SQ |
25 |
196/0.40 |
4 |
1283 |
1.6 |
10.5 |
296 |
CCL-IC-BS6231-35.0SQ |
35 |
276/0.40 |
2 |
1283 |
2.0 |
11.9 |
400 |
CCL-IC-BS6231-50.0SQ |
50 |
396/0.40 |
1 |
1284 |
2.0 |
14.4 |
582 |
CCL-IC-BS6231-70.0SQ |
70 |
360/0.50 |
2/0 |
1284 |
2.0 |
16.7 |
796 |
CCL-IC-BS6231-95.0SQ |
95 |
475/0.50 |
3/0 |
1284 |
2.3 |
19 |
1025 |
CCL-IC-BS6231-120SQ |
120 |
608/0.50 |
4/0 |
1284 |
2.4 |
20.5 |
1282 |
CCL-IC-BS6231-150SQ |
150 |
756/0.50 |
MCM300 |
104 |
2.4 |
23.14 |
1627 |
CCL-IC-BS6231-185SQ |
185 |
925/0.50 |
MCM350 |
104 |
2.4 |
25.4 |
1959 |
CCL-IC-BS6231-240SQ |
240 |
1221/0.50 |
MCM500 |
104 |
2.8 |
28.66 |
2254 |
CCL-IC-BS6231-300SQ |
300 |
1525/0.50 |
MCM600 |
1015 |
- |
31.5 |
3157 |
CCL-IC-BS6231-400SQ |
400 |
2013/0.50 |
MCM800 |
1284 |
- |
36 |
4051 |
|