Heim
Über uns
Produkte
Herunterladen
Technische Lib
Kontakt
Anfrage
Sitemap
Links
 

Alarm u. Audio u. Elektronisches Kabe

Belden gleichwertige Kabel

Koaxial-Kabel

SteuerKabel

LWL Kabel

Flexible Kabel

Instrumentation Kabel

Lan Kabel
EnergieKabel
Bahn-Kabel

Robotik

Rolling Stock Kabel
Gummi u. Kran Kabel
Sicherheit Kabel

Telefon Kabel

Flughafen Kabel

Bus-Kabel

Kabelverschraubungen

Daten Kabel

Heat Detection Kabel
Hochtemperatur-Kabel
Highway Kabel
Marine, Öl, Gas & Petrochemie-Kabel
Special Cables
Spiralkabel
Thermoelement-Kabel
Other Cable
     
  Indoor tight buffer fiber optic cable  
Indoor Used Tight Buffered Fiber
Optical Cable
outdoor multi loose tube fiber optic cable
Outdoor Used Multi Loose Tube
Fiber Optical Cable
 
  Instrumentation Kabel 

Instrumentation Kabel

   1. BS5308 Part 1

BS5308 Part1 Instrumentation Cable Polyethylene Insulated

VDE Ref Code

PVC Sheath Version

LSOH Sheath Version:

RE-2Y(St)Y (Overall Screen)

RE-2Y(St)H (Overall Screen)

RE-2Y(St)Y PiMF(Individual Screen+Overall Screen)

RE-2Y(St)HPiMF(Individual Screen+Overall Screen)

RE-2Y(St)Y-SWA(Overall Screen+Steel Wire Armour)

RE-2Y(St)-SWA(Overall Screen+Steel Wire Armour)

RE-2Y(St)Y PiMF-SWA(Individual Screen+Overall Screen+Steel Wire Armour)

RE-2Y(St)HPiMF-SWA(Individual Screen+Overall Screen+ Steel Wire Armour

Construction

Construction: Annealed solid copper(Class 1),stranded(Class2),

Binder tape:A 23 micron p.e.t.p.tape applied with a

or fiexible(Class 5) to BS5360 .

minimum 50% overlap.

Insulation: Polyethylene to BS 6234 Type 03.

Collective screen:

Pair identification:

Aluminium/p.e.t.p.laminated tape applied with the metallic side

a)Collectively screened cables:Colour coded in

down in electrical contact with a 0.5mm 2 tinned copper

.

accordance with Colour Code Chart 1 on page3

drain wire over the p.e.t.p.binder tape.

b)Individually screened pairs:One blue core and one

Outer protection:

black core in each pair.Pairs identified by numbered

Type 1 Extruded flame retardant PVC sheath.

screen isolation tape.

Type 2 Extruded polyethylene bedding,alvanised steel

Pair screens

wire armour,extruded flame retardant PVC sheath.

Aluminium/p.e.t.p.Laminated tape applied with the metallic

Minimum bending radius:

side down in electrical contact with a 0.5 mm 2 tinned copper drain wire.

Type 1 8 x diameter.

A 23 micron isolation tape is applied over the screening tape with a

Type 2 12xdiameter.

minimum 50% overlap.

Voltage rating

Temperature rating

300 volt core to earth and 500 volt core to core at maximum

During Operation:-40 ℃+70℃

temperature of 65 ℃

During Operation:-0 ℃+50℃

These cables are not for direct connection to the public mains supply

Electrical characteristics

Parameter

Note

Unit

Conductor size

0.5mm 2
(1/0.8mm)

0.5mm 2
(16/0.2mm)

0.75mm 2
(24/0.2mm)

1.0mm 2
(1/1.13mm)

1.5mm 2
(7/0.53mm)

Conductor resistance

max.

Ω/Km

36.8

39.7

26.5

18.2

12.3

Insulation resistance

max.

GΩxKm

5

5

5

5

5

Mutual capacitance at 1 kH
-One pair and two pair(Quad)cables with collective screen and all
cables with individually screened pairs
-Cables with only collective screen except one pair and two pair(Quad)

max.

pF/m

115
75

115
75

115
75

115
75

115
85

Capacitance unbalance at 1 kHz

max.

pF/250m

250

250

250

250

250

Inductance/resistance ratio(L/R)

max.

μH/Ω

25

25

25

25

25

Test voltage

(Core:core)

-

V

V

1000

1000

1000

1000

1000

1000

1000

1000

1000

1000

(Core:core)

Rated voltage

max.

V

300/500

300/500

300/500

300/500

300/500

MULTIPAIR INSTRUMENTATION CABLES(UNARMOURED)
TO BS 5308 PART 1-COLLECTIVELY SCREENED

MULTIPAIR INSTRUMENTATION CABLES(UNARMOURED)TO BS 5308
PART 1 TYPE 1-INDIVIDUAL PAIR AND COLLECTIVELY SCREENED

MULTIPAIR INSTRUMENTATION CABLES(ARMOURED)
TO BS 5308 PART 1 TYPE 2-COLLECTIVELY SCREENED

MULTIPAIR INSTRUMENTATION CABLES(ARMOURED)TO
BS 5308 PART 1 TYPE 2-INDIVIDUAL PAIR AND COLLECTIVELY SCREENED

COLOUR CODE CHART 1

ORDERING OPTIONS

                                         Part 2>>