Instrumentation Cables | ||||||||||||||
|
Instrumentation Cables
Application :
These cables are suitable for internal wiring of appliances and switch, control, metering and instrument panels of
switchgear, etc
Construction
Standards : BS 6231, UL 83, CSA C22.2, UL Flame test UL 1581/VW1 FT1 FT2
Conductor : plain annealed
Insulation : Flexible PVC
Temperature Range: 0 o C -105 o C
Voltage rating : 0.6 / 1kV
Min. Bending radius : 3 x Overall diameter
Insulation colours : 0.5mm² to 25 mm² Red, black, white, grey, brown, orange, yellow, blue, green, and
green/yellow.
35mm² to 120 mm² Red, black and green/yellow. . Other colours available on request.
Relevant Standards :
To BS6231, UL Style 1015, 1028, 1283, 1284; CSA TEW 105 °C; UL VW -1 Vertical Flame Test
Current Ratings
The table below lists the full Thermal current ratings which will raise the Conductor temperature to 85 °C when
one cable is installed in free air at an Ambient temperature of 45 °C.
These ratings are applicable for installations which ensure that the operation of the protective device is not
greater than 1.45 times the continuous current carrying capacity of the cable.
Where protection is by means of semi-enclosed fuses to BS 3036 the rating must be multiplied by a factor of
0.76.
Note:Sizes 150.0mm², 185.0mm² and 240.0mm², 300.0mm² & 400mm² are classed as dual Rated and are
manufactured to UL & BS 6231 only.
SIZE mm² |
RESISTANCE PER 1000M OF 20 °C OHM |
CURRENT RATING AMP |
APPROXIMATE VOLT DROP CONSTANT MV/A/M |
---|---|---|---|
0.5 | 39 | 11 | 46 |
0.75 | 26 | 14 | 31 |
1 | 19.5 | 17 | 22 |
1.5 | 13.3 | 21 | 15 |
2.5 | 7.98 | 30 | 9.1 |
4 | 4.95 | 41 | 5.7 |
6 | 3.3 | 53 | 3.8 |
10 | 1.91 | 75 | 2.2 |
16 | 1.21 | 100 | 1.4 |
25 | 0.78 | 136 | 0.89 |
35 | 0.554 | 167 | 0.64 |
50 | 0.386 | 204 | 0.45 |
70 | 0.272 | 259 | 0.32 |
95 | 0.206 | 321 | 0.24 |
120 | 0.161 | 374 | 0.19 |
150 | 0.129 | 429 | 0.15 |
185 | 0.106 | 496 | 0.13 |
240 | 0.0801 | 595 | 0.092 |
300 | 0.0641 | 680 | 0.073 |
400 | 0.06 | 868 | @70 C 0.145 |
The voltage drop figures are for one cable only. For other circuit arrangements they should be adjusted as follows:
Single-phase 50Hz ac or 2-wire dc circuit's | x2 |
---|---|
Three-phase 50Hz ac circuit's | x1.732 |
BS 6231 Instrumentation Cables
Range & Dimensions for BS 6231 Instrumentation cables
SIZE mm² |
STRANDING mm |
SIZE AWG |
UL STYLE NUMBER |
NOMINAL INSULATION mm |
NOMINAL OVERALL DIAMETER mm |
WEIGHT kg/km |
---|---|---|---|---|---|---|
0.5 | 16/0.20 | 22 | 1015 | 0.8 | 2.6 | 12 |
0.75 | 24/0.20 | 20 | 1015 | 0.8 | 2.8 | 15 |
1 | 32/0.20 | 18 | 1015 | 0.8 | 3 | 18 |
1.5 | 30/0.25 | 16 | 1015 | 0.9 | 3.3 | 23 |
2.5 | 50/0.25 | 14 | 1015 | 1.0 | 3.7 | 34 |
4 | 56/0.30 | 12 | 1015 | 1.0 | 4.4 | 50 |
6 | 84/0.30 | 10 | 1015 | 1.3 | 5.1 | 71 |
10 | 80/0.40 | 8 | 1028 | 1.5 | 6.9 | 123 |
16 | 126/0.40 | 6 | 1283 | 1.5 | 8.6 | 209 |
25 | 196/0.40 | 4 | 1283 | 1.6 | 10.5 | 296 |
35 | 276/0.40 | 2 | 1283 | 2.0 | 11.9 | 400 |
50 | 396/0.40 | 1 | 1284 | 2.0 | 14.4 | 582 |
70 | 360/0.50 | 2/0 | 1284 | 2.0 | 16.7 | 796 |
95 | 475/0.50 | 3/0 | 1284 | 2.3 | 19 | 1025 |
120 | 608/0.50 | 4/0 | 1284 | 2.4 | 20.5 | 1282 |
150 | 756/0.50 | MCM300 | 104 | 2.4 | 23.14 | 1627 |
185 | 925/0.50 | MCM350 | 104 | 2.4 | 25.4 | 1959 |
240 | 1221/0.50 | MCM500 | 104 | 2.8 | 28.66 | 2254 |
300 | 1525/0.50 | MCM600 | 1015 | - | 31.5 | 3157 |
400 | 2013/0.50 | MCM800 | 1284 | - | 36 | 4051 |